| 2011-01-05 10:48:52 | ****PROVISOS**** |
| | ****ISSUED AT CONTRACTOR'S RISK**** |
| | ****REVISION REQUIRED**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | |
| | 1. ACCESSIBLE ENTRANCE DOOR TO COMPLY WITH MANEUVERING |
| | CLEARANCE, FBC 11 FIGURE 25, PULL SIDE. |
| | |
| | 2. REVISE PLAN TO PROVIDE A RAMP DETAIL WHICH COMPLIES |
| | WITH ALL REQUIREMENTS OF FBC 11 4.8. REVISION IS |
| | REQUIRED PRIOR TO FIRST INSPECTION. FOR EXAMPLE, DETAIL |
| | SHOWN DOES NOT SHOW COMPLIANCE (OR DETAIL IS NON |
| | COMPLIANT) WITH REQUIREMENTS SUCH AS EDGE PROTECTION, |
| | RAMP LANDING AT BOTTOM, DOOR MANEUVERING CLEARANCE, |
| | RAMP RISE. |
| | |
| | 3. CLARIFY BUILDING TYPE ON PLAN, II B STATED; NON |
| | COMBUSTIBLE, SEE FBC CHAPTER 6. |
| | |
| | 4. PORCH ENCLOSURE STRUCTURAL DETAIL (PREPARED BY |
| | STEVEN WALSH, PE) TO BE REVIEWED BY ENGINEER OF RECORD |
| | (BERT BEJARANO, PE). |
| | |
| | 5. ACCESSIBLE BATH SHOWN ON FLOOR PLAN CONFLICTS WITH |
| | THE DETAIL MARKED "ACCESSIBLE RESTROOM REQUIREMENTS." |
| | SCOPE OF WORK COVERED UNDER THIS PERMIT IS NOT CLEAR. |
| | REVISE PLAN TO SHOW WORK TO BE INCLUDED IN THIS PERMIT |
| | AND REVISE DETAILS AS NECESSARY.6. |
| | |
| | 6. SUBMIT DOOR PRODUCT APPROVAL. THIS SHOULD BE |
| | REVIEWED BY ENGINEER OF RECORD PRIOR TO SUBMITTAL. |
| | ENGINEER TO SPECIFY DESIGN PRESSURES. |
| | |
| | |
| | |
| | |
| | |