| 2010-03-23 12:32:57 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. DUE TO THE PROXIMITY TO THE INTRACOASTAL, THIS |
| | PARCEL IS LOCATED IN EXPOSURE C (DOES NOT HAVE 1500 |
| | FEET OF STRUCTURES IN ALL DIRECTIONS). PLEASE REVISE. |
| | |
| | 2. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVALS FOR |
| | THE DOORS, FAC9B72. THEY ARE TO BE REVIEWED BY DESIGNER |
| | OF RECORD PRIOR TO SUBMITTAL. |
| | |
| | 3. PLANS STATE THAT THIS STRUCTURE IS A CBS RESIDENCE, |
| | BUT OUR RECORDS SHOW THIS AS AN OFFICE (AND FLOOR PLAN |
| | STATES THIS IS AN OFFICE). PLEASE DECLARE OCCUPANCY |
| | CLASSIFICATION FBC CHAPTER 3. |
| | |
| | 4. IT IS NOT CLEAR HOW THIS IMPROVEMENT WILL AFFECT |
| | ACCESSIBILITY, FBC11-4.1(A). ALSO SEE FBC1008.1.4. |
| | |
| | 5. DECLARE LEVEL OF ALTERATION FBC EXISTING BUILDING |
| | 401.4. |
| | |
| | 6. PLEASE PROVIDE A WALL SECTION INCLUDING INTERIOR |
| | HEIGHT FBC1003.2. NO HURRICANE CONNECTORS ARE SHOWN, |
| | BUT IT APPEARS THAT A NEW INFILL WALL IS PROPOSED, IS |
| | THIS CORRECT? SCOPE NOT CLEAR FBC106, FBC1609. |
| | |
| | 7. DOOR SIZE NOT CLEAR, SEE FBC1008.1.1. THE PLAN |
| | STATES THAT THIS IS A 3' DOOR BUT MASONRY OPENING IS TO |
| | BE 2'9". IS THE DOOR TO BE INSTALLED IN A MASONRY WALL |
| | OR FRAME WALL? PROVIDE A DETAIL FOR THE NEW DOOR |
| | OPENING. |
| | |
| | 8. IF IT IS DETERMINED THAT THIS WAS ENCLOSED WITHOUT A |
| | PERMIT, IMPACT FEE ASSESSMENT FROM PALM BEACH COUNTY |
| | WILL BE REQUIRED. 561-233-5025. |
| | |
| | |
| | |
| | |
| | |