| Plan Review Notes For Permit 10030499 |
| Permit Number |
10030499 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-18 14:39:39 | REROOF BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- ACCORDING TO THE MIAMI-DADE COUNTY WEBSITE MODIFIED | | | BITUMEN NOA 07-0111.03 FILE WAS SUPERSEDED. NEED TO | | | PROVIDE CURRENT NOA. | | | | | | 2- CLEARLY MARK WHICH APPROVED ASSEMBLY AND BASE SHEET | | | FASTENING OPTION IS GOING TO BE INSTALLED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609 FBC | | | 2007. | | | | | | 3- PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY GENERAL | | | LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. IF RAS 117 | | | CALCULATIONS NEED TO BE SIGNED AND SEALED, THEN PROVIDE | | | SIGNED AND SEALED CALCULATIONS. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|