Plan Review Notes
Plan Review Notes For Permit 10030499
Permit Number 10030499
Review Stop B
Sequence Number 1
Notes
Date Text
2010-03-18 14:39:39REROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ACCORDING TO THE MIAMI-DADE COUNTY WEBSITE MODIFIED
 BITUMEN NOA 07-0111.03 FILE WAS SUPERSEDED. NEED TO
 PROVIDE CURRENT NOA.
  
 2- CLEARLY MARK WHICH APPROVED ASSEMBLY AND BASE SHEET
 FASTENING OPTION IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609 FBC
 2007.
  
 3- PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. IF RAS 117
 CALCULATIONS NEED TO BE SIGNED AND SEALED, THEN PROVIDE
 SIGNED AND SEALED CALCULATIONS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  