2010-03-22 08:50:27RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1-FLAT ROOF:
 A) MISSING PRODUCT APPROVAL FOR FLAT ROOF.
  
 B) CLEARLY MARK WHICH APPROVED ASSEMBLY AND BASE SHEET
 FASTENING OPTION IS GOING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 2007 FLORIDA RESIDENTIAL CODE.
  
 C) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 TO MEET THE DESIGN PRESSURES OF SEC.
 R301. IF THE GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED REQUIRES RAS 117 CALCULATIONS TO BE SIGNED
 AND SEALED, THEN PROVIDE SIGNED AND SEALED CALCULATIONS
 (2 COPIES).
 ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO HAVE INTO CONSIDERATION THAT ACCORDING
 TO THE 2009 REVISIONS OF THE 2007 FLORIDA RESIDENTIAL
 CODE, THIS BUILDING IS LOCATED ON EXPOSURE "C".
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  