| 2010-04-01 16:58:28 | 2007 FBC W/2009 REVISIONS | | | MODEL 'E' | | | | | | DENIED BY MECHANICAL | | | | | | 1) SHOW COMPLIANCE WITH FBC R M1602.4 FOR BALANCED | | | RETURN AIR. SHOW LOCATIONS AND SIZES OF TRANSFER DUCTS | | | OR GRILLS IN THE BEDROOMS. | | | | | | 2) SUBMIT SPECIFICATIONS FROM THE MECHANICAL EQUIPMENT | | | MANUFACTURER SHOWING THAT THE EQUIPMENT, APPLIANCES AND | | | SUPPORTS ARE DESIGNED TO RESIST THE WIND PRESSURES | | | GENERATED BY A 140 MPH WIND SPEEDS REQUIRED BY FBC R | | | M1307.3. | | | | | | 3) THE MECHANICAL SYSTEM SIZING SUMMARY DOES NOT MATCH | | | THE SIZE OF THE UNITS SPECIFIED IN THE EQUIPMENT | | | SCHEDULE ON THE MECHANICAL PLANS. | | | | | | 4) NOTE: THE EQUIPMENT SIZING SUMMARY USES WORST CASE | | | ORIENTATION OF THE STRUCTURE. WHEN SUBMITTING FOR | | | INDIVIDUAL PERMITS THE ACTUAL ORIENTATION OF THE | | | STRUCTURE WILL BE REQUIRED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|