| 2010-04-28 10:45:26 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. PLEASE SHOW ALL FIRE RATED WALLS ON THE PLAN. SOME |
| | DETAILS (SUCH AS WALL SECTIONS ON SHEET A1.2) REFER TO |
| | FIRE RATING BUT NONE SHOWN. FBC EB603.1, FBC508.3.3. |
| | PLEASE ALSO CLARIFY WHICH OPENINGS AND PENETRATIONS ARE |
| | TO BE PROTECTED FBC712, FBC715. |
| | |
| | 2. FBC1014.2, SEVERAL ROOMS (SUCH AS 2-112, 2-113, |
| | 2-114, 2-115, 2-002, 2-100, ETC.) WHICH PREVIOUSLY |
| | EXITED DIRECTLY TO THE OUTSIDE NOW EXITS THROUGH WHAT |
| | APPEARS TO BE A COURTYARD. NO INFORMATION WAS PROVIDED |
| | REGARDING THE NEW EXIT PATH. SEE ALSO FBC1026.4.1, |
| | EMERGENCY ESCAPE AND RESCUE FOR CLASSROOMS IF THE NEW |
| | EXIT IS NOT DIRECTLY TO THE OUTSIDE. PLEASE REVISE PLAN |
| | TO SHOW COMPLIANCE FOR NEW MEANS OF EGRESS. |
| | |
| | OTHER ROOMS WHICH PREVIOUSLY EXITED TO THE SOUTH NOW |
| | EXIT TO THE EAST. EXIT DOORS PARTIALLY BLOCK THE |
| | SIDEWALK, AND APPEAR TO DISCHARGE THROUGH THE STAIRS |
| | SHOWN AT THE SOUTHEAST CORNER. CAPACITY OF THE STAIR IS |
| | NOT CLEAR. LIFE SAFETY PLAN SHOULD SHOW EXITING TO THE |
| | PUBLIC WAY AS IT APPEARS THAT OTHER MEANS OF EGRESS |
| | COMPONENTS ARE AFFECTED OR BEING UTILIZED. |
| | |
| | 3. IT IS NOT CLEAR WHICH WALLS ARE EXTERIOR WALLS. SEE |
| | FBC704. FOR INSTANCE, NE PORTION OF PLAN SHOWS TWO |
| | DOUBLE DOORS. IS THERE A ROOF OVER THIS AREA, WITH |
| | WALLS, SO THIS AREA IS INTERIOR? PLEASE CLARIFY |
| | CONIDITIONS THROUGH WHICH EXITING IS NOW REQUIRED BY |
| | NEW LIFE SAFETY PLAN. FBC 1002. |
| | |
| | 4. FBC3105.1.1.1, 7'6" MINIMUM REQUIRED FOR CANOPY, 7' |
| | SHOWN, DETAIL 08-A1.3. |
| | |
| | 5. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| | NEW DOORS, WINDOWS, LOUVERS FAC9B72. |
| | |
| | 6. NEW WINDOWS ARE SHOWN AT THE STAIR. IS THIS A RATED |
| | STAIR? SEE FBC1023, FBC1020 AND SHOW COMPLIANCE ON THE |
| | PLAN. IT IS NOT CLEAR HOW THE PROPOSED IMPROVEMENT WILL |
| | |
| | 7. PLEASE PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. |
| | |
| | 8. A COPY OF THE SOILS INVESTIGATION REPORT WILL BE |
| | REQUIRED PRIOR TO FOUNDATION WORK, FBC1802.2.1 (PROVISO |
| | ITEM). |
| | |
| | |