2010-05-13 14:10:402007 FBC W/2009 REVISIONS
 MODEL 'B' - MASTER
  
 DENIED BY MECHANICAL
  
 1) THE MECHANICAL EQUIPMENT SIZING SUMMARY LISTS A 2.5
 TON UNIT WITH 28.7 MBH SENSIBLE LOAD AND THE PLANS
 SPECIFY A 3.5 TON UNIT WITH A 28.7 MBH SENSIBLE LOAD.
 PLEASE EXPLAIN WHY THE SENSIBLE LOADS ARE NEARLY THE
 SAME AND THE UNITS ARE 1 TON SIZE DIFFERENCE. THE
 SIZING SUMMARY AND PLANS ARE REQUIRED TO CORRESPOND.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW