Notes
Date Text
2010-03-29 16:08:362007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE RETURN AIR TRANSFER DUCT AT THE MASTER BEDROOM
 IS UNDER-SIZED. FBC R M1602.4 REQUIRES TRANSFER DUCTS
 TO BE ONE AND ONE HALF THE CROSS SECTIONAL AREA OF THE
 SUPPLY DUCT ENTERING THE SPACE AND UNDERCUTTING THE
 DOOR ONE INCH. A 14 INCH DIAMETER TRANSFER DUCT IS
 REQUIRED.
  
 2) THE EQUIPMENT SIZING SUMMARY SPECIFIES 30.4 MBH AND
 A 2.5 TON SYSTEM AND THE PLANS SPECIFY 40,000 BTUH AND
 A 3.5 TON SYSTEM. PLEASE CLARIFY.
  
 3) THE EQUIPMENT SIZING CALCULATIONS ARE REQUIRED TO BE
 SITE SPECIFIC, BASED ON THE ORIENTATION OF THE
 DWELLING. WORST CASE CALCULATIONS CAN NOT BE USED.
 THERE ARE EIGHT DIFFERENT POSSIBLE ORIENTATIONS.
  