| 2010-05-13 12:57:02 | 2007 FBC W/2009 REVISIONS |
| | MODEL 'A' - MASTER |
| | |
| | 1) THE COVER SHEET INCORRECTLY LISTS THE 2005 EDITION |
| | OF THE NATIONAL ELECTRICAL CODE AND THE FAIR HOUSING |
| | GUIDELINES. THE 2008 EDITION OF THE NEC IS APPLICABLE |
| | AND FAIR HOUSING GUIDELINES DO NOT APPLY. PLEASE |
| | CORRECT. |
| | |
| | 2) TWO COPIES OF CURRENT PRODUCT APPROVALS FOR EXTERIOR |
| | DOORS, WINDOWS, WINDOW MULLIONS, OVERHEAD GARAGE DOOR, |
| | ROOF SHINGLES, BLOCK LINTELS, HARDI-PLANK, HURRICANE |
| | CONNECTORS/STRAPS, ETC. PER DCA RULE 9B-72. THE |
| | DESIGNER OF RECORD IS REQUIRED TO REVIEW AND APPROVE |
| | THE PRODUCT APPROVALS IN WRITING PER FBC 106.3.3 CITY |
| | AMENDMENTS. |
| | |
| | 3) SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS DRAWINGS |
| | COMPLYING WITH R802.1.6.1 THAT HAVE BEEN REVIEWED AND |
| | APPROVED BY THE STRUCTURAL DESIGNER OF RECORD FOR EACH |
| | OF THE ROOF OPTIONS. |
| | |
| | 4) THE ENERGY CALCULATIONS THAT WERE SUBMITTED DO NOT |
| | LIST THE INTERIOR METAL FRAME ADJACENT WALLS THAT |
| | SEPARATE THE CONDITIONED SPACE FROM THE UNCONDITIONED |
| | GARAGE. PLEASE CORRECT. ALSO CHECK THAT THE CONDITIONED |
| | FLOOR AREA ON THE FORM MATCHES THE A/C AREA THAT IS |
| | SPECIFIED ON THE PLANS. |
| | |
| | NOTE: BECAUSE THESE PLANS ARE TO BE MASTERS, THE |
| | PRODUCT APPROVALS AND TRUSS DRAWINGS ARE REQUIRED TO BE |
| | SUBMITTED FOR REVIEW BEFORE THE MASTERED PLANS ARE |
| | APPROVED. THEY WILL BE FILED WITH THE MASTER AND WILL |
| | NOT BE REQUIRED TO BE SUBMITTED WITH THE PERMITS |
| | APPLIED FOR UNDER THE MASTER. |
| | |