2010-04-28 13:06:07BUILDING PLAN REVIEW
 PERMIT: 10030373
 ADD: 6510 N JOG RD
 CONT: BE& K CONSTRUCTION
 TEL: (561)615-7549
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 APRIL 12/ 2010
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). THE REQUIRED ITEMS
 MAKING UP THIS PROVISO WILL BE CONSIDERED A REVISION,
 WITH SEPARATE REVIEW AND ASSOCIATED FEES.
  
 1) COMPLIED.
  
 2) SHEET S001 BLDG 9043 COMPRESSED AIR SYSTEMS
 STRUCTURAL CONCRETE COMPRESSOR BUILDING CONCRETE ROOF
 PLAN AND SHEET S001 BLDG 9044 CONCRETE WATERPROOFING
 NOTES:
 PLANS DO NOT ACTUALLY INDICATE A ROOFING ASSEMBLY OR
 ROOF COVERING.
 1503.1 GENERAL. ROOF DECKS SHALL BE COVERED WITH
 APPROVED ROOF COVERINGS SECURED TO THE BUILDING OR
 STRUCTURE IN ACCORDANCE WITH THE PROVISIONS OF THIS
 CHAPTER. ROOF COVERINGS SHALL BE DESIGNED, INSTALLED
 AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND THE
 APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF
 COVERING SHALL SERVE TO PROTECT THE BUILDING OR
 STRUCTURE.
  
 1502 DEFINITIONS: ROOF ASSEMBLY. A SYSTEM DESIGNED TO
 PROVIDE WEATHER PROTECTION AND RESISTANCE TO DESIGN
 LOADS. THE SYSTEM CONSISTS OF A ROOF COVERING AND ROOF
 DECK OR A SINGLE COMPONENT SERVING AS BOTH THE ROOF
 COVERING AND THE ROOF DECK. A ROOF ASSEMBLY INCLUDES
 THE ROOF DECK, VAPOR RETARDER, SUBSTRATE OR THERMAL
 BARRIER, INSULATION, VAPOR RETARDER AND ROOF COVERING.
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 ROOFING ASSEMBLIES:
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS: ROOF COVERING!
  
 3) SHEET S001 BLDG 9025 / CONTROL BLDG ACCESS DOOR
 DETAILS: INDICATES A NEW EXTERIOR DOOR BUT NO WIND
 DESIGN INFORMATION WAS PREOVIDED, NOR PRODUCT APPROVAL
 FOR THE EXTERIOR DOOR. 1609.6.2 WIND DESIGN CRITERIA/
 EXTERIOR DOOR ASSEMBLIES NOT COVERED BY SECTION
 1715.4.2 OR SECTION 1714.5.3.1 SHALL BE TESTED FOR
 STRUCTURAL INTEGRITY IN ACCORDANCE WITH ASTM E 330
 PROCEDURE A, AT A LOAD OF 1.5 TIMES THE REQUIRED DESIGN
 PRESSURE LOAD. THE LOAD SHALL BE SUSTAINED FOR 10
 SECONDS WITH NO PERMANENT DEFORMATION OF ANY MAIN FRAME
 OR PANEL MEMBER IN EXCESS OF 0.4 PERCENT OF ITS SPAN
 AFTER THE LOAD IS REMOVED. THE MINIMUM TEST SIZES AND
 MINIMUM DESIGN PRESSURES SHALL BE AS INDICATED IN TABLE
 1714.5.3 .
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved