2010-03-23 09:04:35FAILED
  
 PER PHONE DISCUSSION WITH CHESLEY SHARPE OF BE&K, THE
 STAIRS WILL BE EXTERIOR TO THE BUILDING, THE UREA TANK
 IS NOT IN AN ENCLOSED STRUCTURE, AND THE AIR COMPRESSOR
 STRUCTURE IS A ROOFED STRUCTURE WITH NO WALLS.
  
 1) PLEASE PROVIDE A SITE PLAN SHOWING WHERE THE STAIRS,
 THE UREA TANK AND THE AIR COMPRESSOR STRUCTURE WILL BE
 CONSTRUCTED IN RELATIONSHIP TO THE MANY STRUCTURES AT
 THE GENERATION FACILITY. NOTE: THE SHEET ENTITLED
 "COMPRESSED AIR SYSTEMS STRUCTURAL CONCRETE COMPRESSOR
 BUILDING FOUNDATION PLAN" DOES NOT HAVE A NORTH ARROW,
 SO UNABLE TO ORIENT IN RELATIONSHIP TO THE SITE AERIAL.
  
 2) PLEASE PROVIDE PICTURE(S) OR OTHER VERIFICATION THAT
 NO PARKING, DRIVE AISLE(S) OR LANDSCAPE IS BEING
 REMOVED.
  
 3) THE ADDRESS AND PARCEL CONTROL NUMBERS ON THE PERMIT
 APPLICATION ARE INCORRECT. THEY SHOULD BE 6501 N. JOG
 RD AND 74424234000001010.
  
 4) THE EXTERIOR OF THE UREA TANK AND THE AIR COMPRSSOR
 STRUCTURE WILL REQUIRE A HEDGE AS SCREENING. NOTE: ONCE
 SITE PLAN IS PROVIDED STAFF CAN IDENTIFY WHERE THE
 HEDGE IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.