| 2010-03-29 11:37:06 | | | | WORK IS BEING PERFORMED AT 6501 NORTH JOG ROAD PER THE | | | LETTER FROM JIM WILLIAMS, DISCIPLINE ENGINEER TO | | | CAPTAIN MIKE WILLIAMS DATED MARCH 11, 2010. | | | | | | | | | 1. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO | | | COMPLY WITH NFPA 241. | | | | | | 2. ANY CUTTING OR WELDING OPERATIONS SHALL COMPLY WITH | | | NFPA 51B. | | | | | | 3. ALL WORK SHALL COMPLY WITH THE FLORIDA FIRE | | | PREVENTION CODE, 2007 EDITION. (NFPA 101, NFPA 1, 2006 | | | EDITIONS) | | | | | | 4. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS | | | FOR ALL HANDRAILS AND GUARDRAILS. | | | | | | 5. PLEASE INDICATE STAIR RISE, RUN, AND TREAD DEPTH. | | | | | | 6. WHAT AREA DOES THE STAIR SERVE? | | | | | | 7. PLEASE INDICATE ON THE PLANS THAT THE GUARDS WILL | | | RESIST A 4" SPHERE AND THE BOTTOM ASSEMBLY WILL RESIST | | | A 6" SPHERE. | | | | | | 8. PLEASE INDICATE ANY ASSOCIATED ELECTRICAL | | | INSTALLATIONS FOR THIS PROJECT. | | | | | | 9. PLEASE PROVIDE MATERIAL SAFETH DATA SHEETS (MSDS) | | | FOR THE UREA MATERIAL. PLEASE PROVIDE TANK DETAILS, | | | WARNING LABELS, ETC. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | (561) 804-4724 PHONE | | | (561) 804-4774 FAX | | | |
|