| Plan Review Notes For Permit 10030370 |
| Permit Number |
10030370 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-16 16:06:25 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE EXPLAIN HOW YOU HAVE DETERMINED DESIGN | | | PRESSURES. SEE FBC TABLE R301.2(2) AND (3). 20SF, ZONE | | | 5, -44PSF WITH A COEFFICIENT OF 1.29 (BUILDING 20', | | | EXPOSURE C) MINIMUM PRESSURES IS -56.76. PLEASE REVISE | | | DESIGN PRESSURES AND ANCHORING SPECIFICATIONS AS | | | NECESSARY. | | | |
|