| Plan Review Notes For Permit 10030288 |
| Permit Number |
10030288 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-16 12:24:41 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT | | | SIZE AND TYPE, GROUNDING DETAILS,AND LOAD CALCULATIONS, | | | PER 215.5 NEC, 106.3.5.4 FBC. | | | | | | 2} AN ELECTRICAL CONTRACTOR MUST APPLY FOR AN | | | ELECTRICAL PERMIT PER CHAPTER 489 FS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | FAX/:561/805-6676 | | | |
|