| 2010-03-24 16:18:28 | *****DENIED***** | | | | | | 1) VERIFY ADDRESS OF DEVICES COMPARING FLOOR PLAN TO | | | THE RISER DIAGRAM (IE; PS-50 SHOWN ON THE FLOOR PLAN IN | | | THE BOILER BUILDING IS SHOWN ON THE RISER DIAGRAM OF | | | FLUE GAS BUILDING). | | | | | | 2) ON SHEET FS-13 EXPLAIN, "NO FIRE PROTECTION PROVIDED | | | IN THE ELECTRICAL OR ENGINEER'S ROOM" AS SHOWN IN THE | | | TURBINE BUILDING (ELEVATION 38'-0"). | | | | | | 3) ON SHEET FS-14 ONLY ONE PULL STATION IS SHOWN IN THE | | | BOILER BUILDING AT ELEVATION 24'-0") AND ELEVATION | | | 61'-0". PLEASE EXPLAIN. | | | | | | 4) AS PER LOCAL CODE, DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM. MAKE NECESSARY | | | ADJUSTMENTS TO THE FIRE ALARM MATRIX AND SEQUENCE OF | | | OPERATIONS. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561.805.6722 | | | |
|