| Plan Review Notes For Permit 10030264 |
| Permit Number |
10030264 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-19 15:48:03 | 1641 WORTHINGTON ROAD, SUITE 130 | | | PERMIT NUMBER 10030264 | | | | | | 1. TACTILE SIGNAGE REQUIRED AT EXIT DOOR. | | | | | | 2. ON PAGE A1.0 DASH SYMBOLS SHOW TWO HOUR RATINGS BUT | | | NOTE # 3 SHOWS A ONE HOUR RATING. | | | | | | 3. CARD READERS SHALL NOT INTERFERE WITH ANY EXITING. | | | | | | 4. SEPARATE PLANS AND PERMITS REQUIRED FOR THE | | | PRE-ACTION FIRE SPRINKLER SYSTEM AND THE FM 200 | | | SUPPRESSION SYSTEM. | | | | | | 5. MORE INFORMATION NEEDED REGARDING THE MRSE ROOM. IS | | | THE ROOM CONSIDERED A COMPUTER ROOM. NFPA 75, IS THE | | | STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY | | | EQUIPMENT. SEVERAL CODE REQUIREMENTS EXIST WITHIN THIS | | | STANDARD. PLEASE REVIEW THE SCOPE OF THE STANDARD IN | | | SECTION 1.1. | | | | | | 6. IT APPEARS THAT ONLY ONE FIRE EXTINGUISHER EXISTS. | | | TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 | | | FEET OF TRAVEL DISTANCE. | | | | | | 7. NEW FIRE DAMPERS ARE TO BE DROP TESTED TO ENSURE | | | PROPER OPERATION. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | (561) 804-4709 PHONE | | | (561) 804-4774 FAX |
|