Plan Review Notes
Plan Review Notes For Permit 10030264
Permit Number 10030264
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-03-19 15:48:031641 WORTHINGTON ROAD, SUITE 130
 PERMIT NUMBER 10030264
  
 1. TACTILE SIGNAGE REQUIRED AT EXIT DOOR.
  
 2. ON PAGE A1.0 DASH SYMBOLS SHOW TWO HOUR RATINGS BUT
 NOTE # 3 SHOWS A ONE HOUR RATING.
  
 3. CARD READERS SHALL NOT INTERFERE WITH ANY EXITING.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 PRE-ACTION FIRE SPRINKLER SYSTEM AND THE FM 200
 SUPPRESSION SYSTEM.
  
 5. MORE INFORMATION NEEDED REGARDING THE MRSE ROOM. IS
 THE ROOM CONSIDERED A COMPUTER ROOM. NFPA 75, IS THE
 STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY
 EQUIPMENT. SEVERAL CODE REQUIREMENTS EXIST WITHIN THIS
 STANDARD. PLEASE REVIEW THE SCOPE OF THE STANDARD IN
 SECTION 1.1.
  
 6. IT APPEARS THAT ONLY ONE FIRE EXTINGUISHER EXISTS.
 TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75
 FEET OF TRAVEL DISTANCE.
  
 7. NEW FIRE DAMPERS ARE TO BE DROP TESTED TO ENSURE
 PROPER OPERATION.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774 FAX