2010-03-24 12:56:36BUILDING PLAN REVIEW
 PERMIT: 10030264
 ADD: 1641 WORTHINGTON # 130
 CONT: DPR CONSTRUCTION
 TEL: (561)632-4028
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 GS&P
 GLIDDEN SPINA & PARTNERS
 PHONE: 561-684-5594
  
 PROJECT DOX
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET 1 INDICATES A NEW EXTERIOR DOOR, RULE 9B-72
 AND EXTERIOR METAL DOORS:EXTERIOR DOOR ASSEMBLIES NOT
 COVERED BY SECTION 1715.4.2 OR SECTION 1714.5.3.1 SHALL
 BE TESTED FOR STRUCTURAL INTEGRITY IN ACCORDANCE WITH
 ASTM E 330 PROCEDURE A, AT A LOAD OF 1.5 TIMES THE
 REQUIRED DESIGN PRESSURE LOAD. THE LOAD SHALL BE
 SUSTAINED FOR 10 SECONDS WITH NO PERMANENT DEFORMATION
 OF ANY MAIN FRAME OR PANEL MEMBER IN EXCESS OF 0.4
 PERCENT OF ITS SPAN AFTER THE LOAD IS REMOVED.
 HIGH-VELOCITY HURRICANE ZONES SHALL COMPLY WITH TAS
 202. AFTER EACH SPECIFIED LOADING, THERE SHALL BE NO
 GLASS BREAKAGE, PERMANENT DAMAGE TO FASTENERS, HARDWARE
 PARTS, OR ANY OTHER DAMAGE WHICH CAUSES THE DOOR TO BE
 INOPERABLE.
 THE MINIMUM TEST SIZES AND MINIMUM DESIGN PRESSURES
 SHALL BE AS INDICATED IN TABLE 1714.5.3 .
  
 2) 1609.6.2 WIND DESIGN PROCEDURES
 2.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 2.5) POSITIVE AND NEGATIVE PRESSURES FOR NEW OPENING
  
 2.6) HEIGHT OF BUILDING IN FEET.
  
 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 3.1PAIR OF EXTERIOR METAL DOORS
 3.2 MULLION
 3.3 TRANSOM ABOVE.
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) FLOOR PLAN INDICATES TTHE EXISTING EXIT PAASAGEWAY
 AS TWO HOUR IN DRAWING FORM BUT THE WRITTEN NOTE# 3
 INDICATES THIS WALL TO BE A 1 HR RATED WALL. A FOR
 STORY EXIXT ENCLOSURE WILL QUIRE A 2HR FIRE
 RATING.FBC-B 1020.1/ 1021.3.
  
 6) PLEASE PROVIDE ADDITIONAL INFORMATION FOR ROOM 108
 MRSE THIS ROOM APPEARS TO BE A IT ROOM, IF A TRUE IT
 ROOM THE NEC MAY REQUIRE A 1 HOUR FIRE RATING DEPENDING
 ON WIRING METHODS. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 7) SHEET A3 INDICATES THE USE OF TATE ACCESS FLOORS.
 THE AREA OF CONCERN IS THE FLOOR LOAD ON THE TATE FLOOR
 SYSTEM WITHIN THE COMPUTER ROOM.FBC-B TABLE 1607.1
 COMPUTER ROOMS SHALL BE DESISGNED FOR HEAVIER LOADS
 BASED ON THE ANTICIPATED OCCUPANCY. WILL THERE BE
 CONCENTRATED LOADS ON PANELS THAT MAY CREATE A FAILURE?
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  