| Plan Review Notes For Permit 10030263 |
| Permit Number |
10030263 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-18 17:03:52 | 1641 WORTHINGTON ROAD, SUITE 410 | | | PERMIT # 10030263 | | | FIRST ELECTRONIC PLAN REVIEW FROM PROJECT DOX | | | | | | 1. THE TENANT DEMISING WALL SHALL BE PROPERLY | | | IDENTIFIED WITH "FIRE AND SMOKE BARRIER - PROTECT ALL | | | OPENINGS. SIGNS OR STENCILING WITH AT LEAST 4" HIGH | | | LETTERS, 1/2 " STROKE AND NOT MORE THAN 15 FEET ON | | | CENTER. | | | | | | 2. THE INSTALLATION OF CARD READERS SHALL NOT INTERFERE | | | WITH ANY EXITING. | | | | | | 3. THE PORTABLE FIRE EXTINGUISHERS ON SHEET A-1 SHALL | | | COMPLY WITH NFPA 10, THE STANDARD FOR PORTABLE FIRE | | | EXTINGUISHERS, 2002 EDITION. ALL EXTINGUISHERS SHALL BE | | | PROPERLY SERVICE TAGGED. | | | | | | 4. THE NEW FIRE DAMPER SHALL BE DROP TESTED TO ENSURE | | | PROPER OPERATION. | | | | | | 5. TACTILE SIGNAGE IS REQUIRED AT EXIT DOORS. | | | | | | 6. PLEASE ADVISED ALL UTILITIES THAT ARE PLANNED FOR | | | UNDERNEATH THE RAISED FLOOR. IS ANY FIRE ALARM | | | EQUIPMENT PLANNED OR ANY FIRE SUPPRESSION SYSTEMS | | | CONSIDERED. | | | | | | 7. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE | | | SPRINKLER OR FIRE ALARM SYSTEM REMODELING. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | (561) 804-4724 PHONE | | | (561) 804-4774 FAX | | | |
|