Date Text
2010-03-29 18:50:25PLEASE PROVIDE INFORMATION / CLARIFICATION REGARDING
 "PANEL HEATERS" BOTH PROPOSED AS PART OF THIS PROJECT
 AND THOSE INDICATED AS "FUTURE". PLEASE PROVIDE
 SPECIFICATIONS ON THESE HEATERS, THE ASSOCIATED
 CONTROLS, AND TIMERS AND INFORMATION TO DEMONSTRATE
 THAT THESE DEVICES ARE INCLUDED IN THE BASE BUILDING
 ENERGY CALCUATIONS.
  
 PLEASE CLARIFY HOW ARE THESE HEATERS TO BE CONTROLLED
 BY TIMERS?
  
 PLEASE CHECK INTENDED USE FOR RECEPTACLES / CIRCUIT
 SERVING COUNTERTOP IN EMPLOYEE LOUNGE AREA. IF EITHER A
 MICROWAVE OR COFFEE MACHINE IS DESIRED, DEDICATED
 CIRCUITS MAY BE INDICATED TO AVOID OVERLOADING PROPOSED
 CIRCUITS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY CONCERNS