| 2010-03-16 13:33:23 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. PLEASE REVISE PLAN TO INCLUDE OCCUPANT LOAD BASED ON |
| | NEW SEATING PLAN FBC1004. |
| | |
| | 2. SHOW LIFE SAFETY INFORMATION; EXIT ACCESS TRAVEL |
| | DISTANCE, REQUIRED WIDTH FOR EXITS BASED ON NEW |
| | OCCUPANT LOAD, FBC 10. |
| | |
| | 3. PROVIDE A DETAIL FOR ACCESSIBLE SEATING AND SHOW |
| | COMPLIANCE WITH FBC11-5.1 (5%), FBC11-4.32. NO |
| | DIMENSIONS PROVIDED ON THE PLAN. FOR FIXED SEATING, SEE |
| | FBC11-4.32 AND SHOW CLEAR FLOOR SPACE, AISLE WIDTH, |
| | KNEE CLEARANCE, HEIGHT. |
| | |
| | 4. FBC11-5.2, A "HANDICAP BAR" IS SHOWN ON THE PLAN, |
| | FBC11-4.32.4, BAR IS SHOWN AT 36", MAX 34" PERMITTED. |
| | PLEASE REVISE. |
| | |
| | 5. BOND BREAK REQUIRED FOR STUCCO OVER WOOD SHEATHING |
| | FBC1404.2.1. |
| | |
| | 6. PLAN IS NOT CLEAR. IS THE "VESTIBULE" (ENTRY TOWER) |
| | EXISTING INTERIOR SPACE? PLAN STATES THAT THE ENTRY IS |
| | TO RECEIVE A "NEW CEMENTITIOUS FINISH" OVER EXISTING |
| | PLYWOOD. PLAN ALSO STATES "PROVIDE STUCCO FINISH ON |
| | HIGH RIB LATH OVER NEW SOFFIT" BUT NO DETAIL/WIND |
| | DESIGN CRITERIA PROVIDED FOR THE "NEW SOFFIT," FBC1609, |
| | FBC*106. EXISTING CONDITIONS NOT CLEAR. FBC*106. |
| | |
| | |
| | |
| | |