| Plan Review Notes For Permit 10030231 |
| Permit Number |
10030231 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-18 15:58:06 | *****DENIED***** | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS TO COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | | REFERENCED. | | | | | | 3. SPECIFY THE INTERIOR FINISH MATERIAL NEW WALL IN | | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 4. DOORS WHICH LEAD INTO THE EXIT ACCESS CORRIDOR SHALL | | | BE SELF CLOSING AND SELF LATCHING UPON RELEASE. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|