2010-03-18 14:58:58BUILDING PLAN REVIEW
 PERMIT: 10030231
 ADD: 1400 CENTREPARK SUITE# 310
 CONT: METRO RENOVATIONS
 TEL: (407)234-2269
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE REVIEW THE SIZE LIMITATIONS IN FBC-B
 715.5.7.2 THE TOTAL AREA OF WINDOWS, THIS WOULD ALSO
 INCLUDE THE GLAZING WITHIN THE 45 MINUTE RATED DOOR.
  
 2) PLEASE ALSO REVIEW 715.4.6.4 FOR SAFETY GLAZING
 REQUIREMENTS.
  
 3) THE PLANS FAIL TO IDENTIFY FRAME TYPE FOR BOTH THE
 WINDOW AND DOOR. 715.4.5.1.
  
 4) RATED FIRE DOORS WILL ALSO NEED CLOSEERS. 715.4.7.
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 5) PLANS DO NOT INDICATE THE MINIMUM FLAME SPREAD AND
 SMOKE DEVELOPMENT FBC-B 803.1/ TABLE 803.5.
  
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  