| 2010-03-18 14:58:58 | BUILDING PLAN REVIEW | | | PERMIT: 10030231 | | | ADD: 1400 CENTREPARK SUITE# 310 | | | CONT: METRO RENOVATIONS | | | TEL: (407)234-2269 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PLEASE REVIEW THE SIZE LIMITATIONS IN FBC-B | | | 715.5.7.2 THE TOTAL AREA OF WINDOWS, THIS WOULD ALSO | | | INCLUDE THE GLAZING WITHIN THE 45 MINUTE RATED DOOR. | | | | | | 2) PLEASE ALSO REVIEW 715.4.6.4 FOR SAFETY GLAZING | | | REQUIREMENTS. | | | | | | 3) THE PLANS FAIL TO IDENTIFY FRAME TYPE FOR BOTH THE | | | WINDOW AND DOOR. 715.4.5.1. | | | | | | 4) RATED FIRE DOORS WILL ALSO NEED CLOSEERS. 715.4.7. | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | 5) PLANS DO NOT INDICATE THE MINIMUM FLAME SPREAD AND | | | SMOKE DEVELOPMENT FBC-B 803.1/ TABLE 803.5. | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE | | | CUSTOMER SERVICE SURVEY AT: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | |
|