| Plan Review Notes For Permit 10030199 |
| Permit Number |
10030199 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-31 09:53:06 | | | | 512 SPENCER DRIVE | | | PERMIT NUMBER 10030199 | | | NEW CONSTRUCTION OF A TWO STORY PRESS BOX | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | 2. DOOR SCHEDULE APPEARS TO BE INCORRECT. SCORE KEEPER | | | DOOR NUMBER APPEARS TO BE INCORRECT. | | | | | | 3. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS | | | FOR HANDRAILS AND CHAIN LINK FENCING. | | | | | | 4. WHAT ITEMS WILL BE CONTAINED IN THE FIRST FLOOR | | | STORAGE AREA. | | | | | | 5. ON PAGE A-5, GENERAL NOTES # 1 IT REFERENCES EXIT | | | SIGNS AND EMERGENCY LIGHTS HOWEVER NON ARE SHOWN. | | | | | | 6. PLEASE DESCRIBE ALL SAFETY EQUIPMENT FOR THE | | | BUILDING. | | | | | | 7. PLEASE DESCRIBE SLIP RESISTANT MEASURES FOR STAIRS. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | (561) 804-4709 PHONE | | | (561) 804-4774 FAX | | | | | | WESLEY JOLIN, FIRE PROTECTION ENGINEER | | | BUREAU OF FIRE PREVENTION | | | (561) 804-6730 PHONE | | | (561) 804-4774 FAX |
|