Plan Review Notes
Plan Review Notes For Permit 10030199
Permit Number 10030199
Review Stop B
Sequence Number 1
Notes
Date Text
2010-04-06 10:39:10BUILDING PLAN REVIEW
 PERMIT: 10030199
 ADD: 512 SPENCER DRIVE
 CONT: CANO, INC
 TEL: (561)543-1290
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 DESIGNER: ARCHITECT FERNANDO PRIETO
 PHONE: (561) 248-8809
 DATE 3-30-2010
 1ST REVIEW
 ACTION: DENIED
  
 1) CONTRACTOR TO CORRECT THE DESCRIPTION OF PROJECT ON
 THE PERMIT APPLICATION FORM FROM A PRESS BOX TO SCORERS
 STATION. IF PRESS BOX REMAINS THEN EITHER A LIFT OR
 ELEVATOR WILL BE REQUIRED. VERTICAL ACCESSIBILITY
 11-4.1.3(5).
  
 2) CONTRACT VALUE IS EXTREMELY LOW, IT CAN NOT BE
 DETERMINED SINCE THE OCCUPANCY CLASSIFICATION NEEDS TO
 BE ADDRESSED. ONCE THIS IS REVIEWED THE NEW VALUE WILL
 BE ASSIGNED USING:
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) SHEET A-4 INDICATES THIS BUILDING TO BE AN
 EDUCATIONAL USAGE. IT APPEARS TO BE A MIXED USAGE SINCE
 100% OF THE FIRST FLOOR IS STORAGE, PLEASE INDICATE IF
 IT IS A S1OR S2 STORAGE.
 SECTION 311.2 & 311.3.
  
 4) SHEET A-4 DESIGN CRITERIA FOR BUILDING CODE
 COMPLIANCE DOES NOT PROVIDE MINIMUM BUILDING DESIGN
 TYPE PER TABLE 503, NOTE A TYPE V-B CANNOT BE A
 EDUCATIONAL USAGE ON THE SECOND FLOOR UNLESS FIRE
 SPRINKLERED. SEE 504.2.
  
 5) SHEET A-4 THE DESIGN PRESSURES FOR ALL OPENINGS ARE
 LOW FOR A ???C??? EXPOSURE FOR INTERIOR ZONES AS WELL
 AS END ZONES. PLANS INDICATE THE MEAN ROOF HEIGHT OF
 12???-0??? WHERE AS THE MEAN ROOF HEIGHT IS 21???-3???.
 THIS RESULTS IN A MUCH HIGHER MULTIPLIER A 1.29
 .1609.1.1 DETERMINATION OF WIND LOADS. WIND LOADS ON
 EVERY BUILDING OR STRUCTURE SHALL BE DETERMINED IN
 ACCORDANCE WITH CHAPTER 6 OF ASCE 7-05. PLEASE REVIEW
 ASCE 7-05 FIGURE 2 ADJUSTMENT FACTORS. AT THIS TIME THE
 SUBMITTED PRODUCT APPROVALS CAN NOT BE REVIEWED UNTIL
 PRESSURES ARE CORRECTED.
  
 6) C.H.I. OVERHEAD DOORS- PLEASE CIRCLE WHICH MODEL
 DOOR IS TO BE INSTALLED SINCE EACH TYPE HAS DIFFERENT
 PRESSURES.
  
 7) SHEET A-2 SOUTHWEST ELEVATION INDICATES THE USE OF
 EXTERIOR STAIRS. PLEASE REVIEW:
 1023.6 EXTERIOR STAIRWAY PROTECTION. EXTERIOR EXIT
 STAIRWAYS SHALL BE SEPARATED FROM THE INTERIOR OF THE
 BUILDING AS REQUIRED IN SECTION 1020.1. OPENINGS SHALL
 BE LIMITED TO THOSE NECESSARY FOR EGRESS FROM NORMALLY
 OCCUPIED SPACES.
 A ONE HOUR RATING IS REQUIRED PLEASE SEE CODE
 COMMENTARY FIGURE 1023.6(1).SEE ATTACHED SHEET. THE
 SUBMITTED JELD-WEN REPORT NOA07-0709.07 DOES NOT
 INCLUDE FIRE TESTING A SECOND REPORT WILL BE REQUIRED (
 UL OR OTHER APPROVED AGENCY). SWCTION 715, TABLE 715.4
 & 715.4.7.
  
 8) SHEET A-4 INDICATES THE DESIGN CRITERIA FOR THE ROOF
 TRUSSES BUT THE PLANS DON???T PROVIDE
 THE DESIGN CRITERIA FOR THE 2ND FLOOR, FLOOR TRUSSES,
 SPACING, LOADING PER TABLE 1004.1.1.
  
 9) EXTERIOR STAIR DESIGN CRITERIA IS ALSO IS MISSING
 TABLE 1004.1.1.
  
 10) SINCE THERE WAS NO DESIGN CRITERIA PROVIDED PLEASE
 BE AWARE OF 11-4.9.2 OPEN RISERS ARE NOT PERMITTED.
 11-4.9.2 TREADS AND RISERS. ON ANY GIVEN FLIGHT OF
 STAIRS, ALL STEPS SHALL HAVE UNIFORM RISER HEIGHTS AND
 UNIFORM TREAD WIDTHS. STAIR TREADS SHALL BE NO LESS
 THAN 11 INCHES (280 MM) WIDE, MEASURED FROM RISER TO
 RISER [SEE FIGURE 18(A)]. OPEN RISERS ARE NOT
 PERMITTED.
  
 11) THE SCOREKEEPERS STATION MAY NOT REQUIRE VERTICAL
 ACCESSIBILITY BUT THE STAIRS MUST BE DESIGNED AS
 ACCESSIBLE STAIRS . HANDRAILS: 11-4.9.4 HANDRAILS.
 STAIRWAYS SHALL HAVE HANDRAILS AT BOTH SIDES OF ALL
 STAIRS. HANDRAILS SHALL COMPLY WITH SECTION 11-4.26 AND
 SHALL HAVE THE FOLLOWING FEATURES:(2) IF HANDRAILS ARE
 NOT CONTINUOUS, THEY SHALL EXTEND AT LEAST 12 INCHES
 (305 MM) BEYOND THE TOP RISER AND AT LEAST 12 INCHES
 (305 MM) PLUS THE WIDTH OF ONE TREAD BEYOND THE BOTTOM
 RISER. AT THE TOP, THE EXTENSION SHALL BE PARALLEL WITH
 THE FLOOR OR GROUND SURFACE. AT THE BOTTOM, THE
 HANDRAIL SHALL CONTINUE TO SLOPE FOR A DISTANCE OF THE
 WIDTH OF ONE TREAD FROM THE BOTTOM RISER; THE REMAINDER
 OF THE EXTENSION SHALL BE HORIZONTAL [SEE FIGURE 19(C)
 AND FIGURE 19(D)]. HANDRAIL EXTENSIONS SHALL COMPLY
 WITH SECTION 11-4.4.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved