Plan Review Notes
Plan Review Notes For Permit 10030189
Permit Number 10030189
Review Stop P
Sequence Number 1
Notes
Date Text
2010-03-11 14:08:32RESIDENTIAL (R3) PLUMBING REVISION.
 2007 FLORIDA RESIDENTIAL BUILDING CODE WITH 2009
 REVISIONS.
  
 1- PLUMBING RISER DIAGRAM IS MISSING THE NEW SHOWER
 THAT WAS ADDED TO THE MASTER BEDROOM BATH.
  
 2- REVISE PLUMBING RISER DIAGRAM TO COMPLY WITH SEC.
 P3108.1 OF 2007 FLORIDA RESIDENTIAL CODE. BATHROOM
 FIXTURES AND LAUNDRY FIXTURES CAN NOT BE CONNECTED TO
 THE SAME WET VENT. THEY NEED TO BE ON ANOTHER STACK
 DOWNSTREAM OF THE BATHROOM HORIZONTAL WET VENT. READ
 SEC. P3108.1 AND REVISE AS REQUIRED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712