2010-03-08 14:09:17RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- A) CLEARLY MARK WHICH BASE SHEET FASTENING OPTION IS
 GOING TO BE INSTALLED.
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. OWES $75.16 FOR UPDATE VALUATION AS REQUIRED BY
 SEC. 108.3 CITY AMENDMENTS TO FBC.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712