Plan Review Notes
Plan Review Notes For Permit 10030174
Permit Number 10030174
Review Stop B
Sequence Number 1
Notes
Date Text
2010-03-10 09:55:03BUILDING PLAN REVIEW
 PERMIT: 09090440/ REV 10030174
 ADD: 836 BELVEDERE
 CONT: US GENERAL
 TEL: (503)577-8237
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 PRODUCT APPROVAL REVIEW& SHOP DRAWING WINDOW/ DOOR
 REVIEW
  
 SUBMITTED PRODUCT APPROVAL REPORTS & SHOP DRAWINGS
 1) STOREFRONT NOA 05-0906.04
  
 2) PASS-THRU NOA 08-1210.04- MISSING THE TECHNICAL
 DRAWINGS ASSOCIATED WITH NOA/ +70/-80 BUILDING APPROVED
 WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 3) ARCH OUT-SWING DOORS NOA 09-0105.01
 4) CURRIES STEEL DOOR NOA 09-0226.10
 5) STO- PLYWOOD NOA 07-0104.04
 6) STO-CMU NOA 07-0104.05
  
  
  
 7) ROOFTOP A/C STAND NOA 07-0509.09
 DENIED!
  
 PRODUCT APPROVAL IS MISSING THE TECHNICAL SHEETS
 ASSOCIATED WITH THIS NOA.
 NOTE THE NOA PRESSURE FOR A SSTEEL ROOF JOIST STRUCTURE
 ARE 53.2
 THE ENGINEERING SHEET FROM FRANK BENNARDO P. E., SITE
 SPECIFIC STATES INFORMATIONAL ONLY AND WILL NEED TO BE
 SIGNED AND SEALED!
  
  
  
 8) WINDOW/ DOOR SHOP DRAWINGS JAMES BUSHOUSE P. E.