| Plan Review Notes For Permit 10030114 |
| Permit Number |
10030114 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-17 10:32:45 | 1. W.C. STALL IN WOMENS ROOM REQUIRED TO BE PER 11-4.17 | | | FIG. 30(E) WITH LAV IN STALL. | | | | | | 2. PLUMBING PLAN SHOWS HORIZONTAL DRY VENT IN WOMENS | | | ROOM BETWEEN WATER CLOSETS. FBC 2007 PLUMBING 905.3 & | | | 905.4 | | | VENTS SHALL RISE VERTICALLY TO A MINIMUM OF 6 INCHES | | | ABOVE FLOOD LEVEL RIM OF FIXTURE. | | | | | | LARRY WAGNER | | | CHIEF PLUMBING | | | 805-6692 | | | [email protected] |
|