| Plan Review Notes For Permit 10030093 |
| Permit Number |
10030093 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-29 13:34:43 | | | | 529-21ST STREET | | | | | | 1. NEW DOORS FOR THE APARTMENTS SHALL BE AT LEAST 20 | | | MINUTE FIRE RATED. "DOORS THAT OPEN ONTO EXIT ACCESS | | | CORRIDORS, OTHER THAN THOSE COMPLYING WITH 8.3.4 OR IN | | | BUILDINGS MEETING 31.3.6.2. SHALL HAVE NOT LESS THAN | | | THAN A 20 MINUTE FIRE PROTECTION RATING IN ACCORDANCE | | | WITH SECTION 8.3. RE: FFPC SECTION 31.3.6.2.1. (NFPA | | | 101, 2006 EDITION) | | | | | | 2. BUILDINGS ARE NOT OPTION 3 WITH FIRE SPRINKLERS IN | | | SELECTED AREAS OR OPTION 4 WITH COMPLETE FIRE SPRINKLER | | | SYSTEMS. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | (561) 804-4724 PHONE | | | (561) 804-4774 FAX |
|