| Plan Review Notes For Permit 10030068 |
| Permit Number |
10030068 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-09 14:55:40 | ****PROVISO**** | | | ****REVISION REQUIRED PRIOR TO FIRST INSPECTION**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, | | | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING | | | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR | | | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING | | | CANNOT BE REDUCED BY MORE THAN 5%. | | | | | | 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR | | | THE DOOR, FAC9B72. | | | | | | 3. WHEN SUBMITTING THE REVISION, TWO COMPLETE SETS OF | | | DOCUMENTS REQUIED. | | | | | | |
|