| 2010-03-08 12:47:46 | |
| | |
| | REVISION DENIED/INCOMPLETE INFORMATION |
| | |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} SHEET E-2 IS MISSING THE RISER DIAGRAM, ELECTRICAL |
| | NOTES AND LEGEND, PANEL SCHEDULES AND LOAD |
| | CALCULATIONS. ALSO THE PLUMBING DIAGRAM HAS BEEN |
| | REMOVED, SUBMIT NEW PLUMBING PLANS TO SHOW THE |
| | REVISIONS TO THE PLAN.105.1 FBC AS AMENDED. |
| | |
| | 2} POOL EQUIPMENT HAS BEEN ADDED, A SEPARATE POOL |
| | PERMIT IS REQUIRED FOR THIS WORK, THE LOAD CALCULATIONS |
| | AND PANEL SCHEDULE MUST BE REVISED. 105.1FBC. |
| | |
| | 3} THE METER LOCATION HAS BEEN REMOVED FROM SHEET E-1, |
| | INDICATE LOCATION OF SAME SO THAT COMPLIANCE WITH |
| | ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. THE AREA ON |
| | EITHER SIDE OF THE RANGE DO NOT APPEAR TO COMPLY WITH |
| | THE 2' SPACING. |
| | |
| | 5} THE PANEL INROOM 104 "LAUNDRY, 2ND FLOOR, IS IN |
| | VIOLATION OF ARTICLE 110.26(A)(2) WIDTH OF WORKING |
| | SPACE THE WIDTH OF THE WORKING SPACE IN FRONT OF THE |
| | ELECTRIC EQUIPMENT SHALL BE THE WIDTH OF THE EQUIPMENT |
| | OR 750 MM (30 IN.), WHICHEVER IS GREATER. IN ALL CASES, |
| | THE WORK SPACE SHALL PERMIT AT LEAST A 90 DEGREE |
| | OPENING OF EQUIPMENT DOORS OR HINGED PANELS.SEE SHEET |
| | A-2 FOR DIMENSION OF THAT SPACE (2'-31/4") |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |