| Plan Review Notes For Permit 10030036 |
| Permit Number |
10030036 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-04 19:24:27 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PROVIDE VENTILATION CALCULATIONS FOR THE PROPOSED | | | RECONFIGURED SPACES AND THE PROPOSED NEW USE AND | | | OCCUPANT LOADS PER FBC-EB 709.1 AND FBC-EB 901.2. | | | | | | 2. PROVIDE MISSING DUCT SIZE FOR SUPPLY TRUNK LINE ON | | | EXISTING SOUTH PACKAGE UNIT PER FBC-M 603.1. | | | | | | 3. AUXILIARY DRAIN PROTECTION IS REQUIRED ON NEW | | | PACKAGE UNIT PER FBC-M 307.2.3.1. | | | | | | 4. VENTILATION RATES ARE LIKELY TO INCREASE DUE TO | | | INCREASED OCCUPANT LOADS (COMMENT #1). MOTORIZED VOLUME | | | DAMPERS WITH SHUTOFF DAMPER CONTROLS ARE REQUIRED ON | | | OUTSIDE AIR INTAKES PER FBC-B 13-409.AB.3.3. | | | | | | 5. PROVIDE MANUFACTURER'S DATA SHOW NEW RTU IS DESIGNED | | | FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. | | | | | | NOTE: SEPARATE PLANS AND PERMIT APPLICATIONS ARE | | | REQUIRED FOR THE FOLLOWING SYSTEMS: | | | | | | KITCHEN HOOD | | | HOOD SUPPRESSION | | | WALK-IN COOLER. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|