2010-03-04 19:24:27REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE VENTILATION CALCULATIONS FOR THE PROPOSED
 RECONFIGURED SPACES AND THE PROPOSED NEW USE AND
 OCCUPANT LOADS PER FBC-EB 709.1 AND FBC-EB 901.2.
  
 2. PROVIDE MISSING DUCT SIZE FOR SUPPLY TRUNK LINE ON
 EXISTING SOUTH PACKAGE UNIT PER FBC-M 603.1.
  
 3. AUXILIARY DRAIN PROTECTION IS REQUIRED ON NEW
 PACKAGE UNIT PER FBC-M 307.2.3.1.
  
 4. VENTILATION RATES ARE LIKELY TO INCREASE DUE TO
 INCREASED OCCUPANT LOADS (COMMENT #1). MOTORIZED VOLUME
 DAMPERS WITH SHUTOFF DAMPER CONTROLS ARE REQUIRED ON
 OUTSIDE AIR INTAKES PER FBC-B 13-409.AB.3.3.
  
 5. PROVIDE MANUFACTURER'S DATA SHOW NEW RTU IS DESIGNED
 FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12.
  
 NOTE: SEPARATE PLANS AND PERMIT APPLICATIONS ARE
 REQUIRED FOR THE FOLLOWING SYSTEMS:
  
 KITCHEN HOOD
 HOOD SUPPRESSION
 WALK-IN COOLER.
  