| 2010-03-15 13:00:56 | FIRE STATION # 5 AND EMERGENCY OPERATIONS CENTER |
| | 700 NORTH CONGRESS AVENUE |
| | DESIGN ANALYSIS-PHASE II SUBMITTAL |
| | PERMIT # 10030034 |
| | |
| | 1. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO |
| | COMPLY WITH NFPA 241. |
| | |
| | 2. TEMPORARY DRIVEWAYS SHOWN ON PAGE C-PD.02 SHALL NOT |
| | INTERFERE WITH EMERGENCY OPERATIONS. |
| | |
| | 3. SEPARATE PLANS AND PERMITS REQUIRED FOR UNDERGROUND |
| | DEISEL AND LIQUFIED PETROLEUM GAS TANKS. |
| | |
| | 4. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | RELOCATION OF THE EXISTING GENERATOR IN PHASE I. |
| | |
| | 5. A DEMOLITION PERMIT AND UTILITY LETTERS ARE REQUIRED |
| | PRIOR TO THE DEMOLITION OF THE EXISTING STATION. |
| | |
| | 6. FIRE MAIN SIZES ARE NOT CALLED OUT ON PAGE C-WS.02. |
| | |
| | 7. ALL FIRE HYDRANTS SHALL BE PROVIDED WITH THE PROPER |
| | CLEARANCES. |
| | |
| | 8. EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION. |
| | |
| | 9. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD, |
| | DUCT, AND FIRE SUPPRESISON SYSTEM. |
| | |
| | 10. ONLY ONE FIRE EXTINGUISHER SHOWN NEAR THE ICE MAKER |
| | ON PAGE LS-1 IS NEEDED. THE OTHER SHOULD BGE RELOCATED |
| | TO THE ADMINISTRATION AREA. |
| | |
| | 11. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOORS. |
| | |
| | 12. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE |
| | ALARM SYSTEM. THE REQUIRED FIRE ALARM SYSTEM SHALL BE |
| | MONITORED BY A LICENSED CENTRAL STATION THAT IS THIRD |
| | PARTY CERTIFICATED. |
| | |
| | 13. PLEASE PROVIDE DIAGONAL DIMENSIONS FOR THE BUILDING |
| | THAT ILLUSTRATE THAT THE EXITS ARE AT LEAST 1/3 THE |
| | DISTANCE APART. |
| | |
| | 14. THE HOOD SHAFT APPEARS TO TRAVEL THROUGH THE |
| | BUNKROOM ON THE SECOND FLOOR NEAR THE DOORWAY. PLEASE |
| | EXPLAIN RATIONALE. |
| | |
| | 15. ALL FIRE RATED WALLS ARE TO BE PROPERLY IDENTIFIED |
| | AS FIRE WALLS AND ALL OPENINGS ARE REQUIRED TO BE |
| | PROTECTED. |
| | |
| | 16. A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. |
| | |
| | 17. KNOX-BOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE |
| | DEPARTMENT CONNECTION (FDC). |
| | |
| | 18. THE BUILDING ADDRESS IS REQUIRED ON THE PROPER |
| | ELEVATION. A MINIMUM OF AT LEAST 6" HIGH AND AT LEAST |
| | 1" WIDE NUMBERS ARE REQUIRED. |
| | |
| | 19. ELEVATOR WARNING SIGNS ARE REQUIRED AT EACH |
| | ELEVATOR LOBBY. |
| | |
| | 20. ALL FIRE DAMPERS AFTER INSTALLATION SHALL BE DROP |
| | TESTED TO ENSURE PROPER OPERATION. |
| | |
| | 21. THE KITCHEN EXHAUST FAN SHALL BE A MINIMUM OF AT |
| | LEAST 10 FEET FROM THE KITCHEN SUPPLY FANS. |
| | |
| | 22. ON PAGE E-0.01, PLEASE PROVIDE PROPER EDITIONS TO |
| | CODES CITED. |
| | |
| | 23. TAMPER SWITCHES SHOWN ON PAGE E-0.02 ARE IN THE |
| | INCORRECT LOCATION. THESE TAMPER SWITCHES SHOULD BE ON |
| | THE NORTH SIDE NOT THE SOUTH SIDE. |
| | |
| | 24. PLEASE ILLUSTRATE ON SHEET E-2.01 WHERE THE |
| | EMERGENCY LIGHTS ARE LOCATED IN THE KITCHEN AND GREAT |
| | ROOM. |
| | |
| | 25. IT APPEARS THAT NONE OF THE RESTROOMS HAVE ANY |
| | EMERGENCY LIGHTS. ARE THESE LIGHTS CONNECTED TO THE |
| | GENERATOR. |
| | |
| | 26. ARE THE BUNKROOM INDIVIDUAL ROOMS. IF SO WHY ARE NO |
| | SMOKE DETECTORS PROVIDED. |
| | |
| | 27. NO EMERGENCY LIGHT FIXTURE COULD BE LOCATED NEAR |
| | MEZZANINE STAIRS. |
| | |
| | 28. ELECTRICAL PANEL DIRECTORIES ON PAGE E-6.01 NEED TO |
| | BE COMPLETED. |
| | |
| | 29. ON PAGE E-7.01, THE FIRE ALARM RISER INDICATES A |
| | DEDICATED TELEPHONE CONNECTION. PLEASE BE ADVISED THAT |
| | TWO PHONE LINES ARE REQUIRED WITH 2 RJ31X JACKS. |
| | |
| | 30. THE FIRE DEPARTMENT CONNECTION SHOWN ON PAGE |
| | FP-0.02 IS SHOWN IS A DIFFERENT LOCATION AND IS FACING |
| | TOWARDS THE PARKING AREA INSTEAD OF THE DRIVEWAY. |
| | |
| | 31. ON PAGE P-2.01 PLUMBING PIPES ARE NOTED IN STAIR |
| | 3.52. THIS IS AN EXIT STAIR. |
| | |
| | 32. SECUIRTY DEVICES PLANNED FOR DOORS AS ILLUSTRATED |
| | ON PAGE T-2.05 SHALL COMPLY WITH SPECIAL LOCKING |
| | ARRANGEMENTS OF THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 33. NFPA 75 SHALL BE NOTED ON THE PLANS. THE IT ROOM |
| | AND THE MIS ROOM SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 75. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | 804-4709 PHONE |
| | 804-4774 FAX |