Date Text
2010-03-16 14:02:302007 FBC W/2009 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) THE PLANS SPECIFY THE STRUCTURE AS BEING EXPOSURE
 CATEGORY "B". HOWEVER, IT IS EXPOSURE "C". PLEASE
 CORRECT AND REVISE COMPONENT AND CLADDING PRESSURES TO
 REFLECT EXPOSURE "C". SEE FBC R301.2.1.4.3.
  
 2) ON THE SOME OF THE DRAWINGS PORTIONS OF THE EXISTING
 STRUCTURE ARE FADED OUT. PLEASE CORRECT.
  
 3) THE TRUSS CONNECTOR SCHEDULE ON SHEET A-3 LISTS TC-1
 AS A USP RT 16 WITH 4 TAP-CONS TO THE TIE BEAM AND 700#
 UPLIFT. THE SPECIFIED UPLIFTS AT THE HIP GIRDERS EXCEED
 700#. PLEASE CORRECT. THE USP CATALOG LISTS AN RT16M
 FOR RETROFIT MASONRY APPLICATIONS WITH 1395# OF UPLIFT,
 WHICH COULD BE USED. IT APPEARS THAT EMBED STRAPS COULD
 BE USED TO ANCHOR THE TRUSSES TO THE NEW MASONRY WALLS
 AS SHOWN IN DETAIL 1 ON A-3.
  
 4) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 TRUSS CONNECTORS THAT WILL BE USED AS REQUIRED BY DCA
 RULE 9B-72.
  
 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 106.3.3 CITY AMENDMENTS.
  
 6) SHOW COMPLIANCE WITH FBC R320 FOR TERMITE
 PROTECTION.
  
 7) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  