| Plan Review Notes For Permit 10020549 |
| Permit Number |
10020549 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-04-05 14:10:43 | ****PROVISO**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. WALL MOUNT 2 (WHICH WAS HIGHLIGHTED BUT NOT | | | SPECIFIED AS SHUTTER MOUNTING CONNECTION TYPE) REQUIRES | | | 9" FOR BOTTOM WITH .5 COEFFICIENT FOR 2" EDGE DISTANCE. | | | INSTALLATION SCHEDULE HAS BEEN REDLINED FOR 6" TOP, 4" | | | BOTTOM. | | | | | | 2. TOP CONNECTION REQUIRES CONCRETE SUBSTRATE. IF | | | CONCRETE SUBSTRATE CANNOT BE VERIFIED, REVISE | | | INSTALLATION SCHEDULE. SEE PAGE 10 AND 11, MASONRY | | | SUBSTRATE NOT PERMITTED. | | | | | | 3. ANCHOR SPACING DOES NOT COMPLY WITH WALL PRESSURES | | | PROPOSED (+-80PSF, -130PSF). INSTALLATION SCHEDULE HAS | | | BEEN REDLINED FOR DESIGN PRESSURE OF +-60PSF. | | | | | | | | | | | | | | | |
|