2010-03-08 08:57:59****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE INSTALLATION SCHEDULE IS NOT CONSISTENT WITH THE
 INFORMATION HIGHLIGHTED ON THE PRODUCT APPROVAL, AND
 DOES NOT COMPLY WITH THE MINIMUM REQUIREMENTS OF THE
 PRODUCT APPROVAL. FOR INSTANCE:
  
 A. 2" EDGE DISTANCE SPECIFIED, SEE SHEET 9 - THIS
 REQUIRES A .50 FACTOR (MULTIPLY ANCHOR SPACING ON THE
 CHART BY .50).
  
 B. SEE SHEET 9, SOLID SET HIGHLIGTED, BUT NOT SPECIFIED
 ON THE "SPECIFIC ANCHOR TYPE". ONE OF THE OPTIONS ON
 THE PRODUCT APPROVAL MUST BE USED OR ENGINEERING
 PROVIDED.
  
 C. "+-40 OR LESS" CHART WAS USED, BUT DESIGN PRESSURES
 REQUIRED EXCEED -40 FOR SOME OPENINGS. SEE SHEET 10 -
 THESE CHARTS SHOULD BE USED FOR DESIGN PRESSURES
 BETWEEN -40 AND -60. THE CHART USED ON SHEET 9 WOULD BE
 COMPLIANT ONLY FOR OPENINGS SUCH AS 1, 2, 5, ETC. WHERE
 NEGATIVE DESIGN PRESSURES ARE LESS THAN 40.
  
 D. IT IS NOT CLEAR WHICH CONNECTION TYPE IS PROPOSED. 7
 (TOP) AND 7(BOTTOM) ARE HIGHLIGHTED; PLEASE CONFIRM.
 THIS CONNECTION TYPE IS NOT ALLOWED FOR SOLID SET,
 MASONRY SUBSTRATE. A SUBSTRATE IS "MASONRY" IF IT IS A
 FILLED CONCRETE BLOCK. IF "CONCRETE" IS SPECIFIED,
 INFORMATION REGARDING HOW THIS SUBSTRATE HAS BEEN
 CONFIRMED WILL BE REQUIRED (FORMED AND POURED TIE BEAM
 RATHER THAN BOND BEAM).
  
 DUE TO CONFLICTING INFORMATION PROVIDED (INSTALLATION
 SCHEDULE DOES NOT MATCH INFORMATION ON PRODUCT
 APPROVAL) A COMPLETE REVIEW CANNOT BE DONE AT THIS
 TIME. PLEASE CHECK ALL INFORMATION PRIOR TO
 RESUBMITTAL.
  