| 2010-03-22 14:34:02 | MECHANICAL PLAN REVIEW COMMENTS: |
| | |
| | 1. ASHRAE -62-04 FRESH AIR CALCULATION - THE SPACE HAS |
| | BEEN IMPROPERLY CLASSIFIED PURSUANT TO EITHER ASHRAE |
| | 62-04 OR FBCM AS A "MERCANTILE" SPACE. THIS IS THE |
| | BUILDING CODE CLASSIFICATION OF THE PROPOSED OCCUPANCY |
| | AND IS NOT APPLICABLE TO THE REQUIRED VENTILATION RATES |
| | FOR THE INTENDED USE. PLEASE REVISE THE FRESH AIR |
| | CALCULATIONS TO ACCURATELY REFLECT THE USAGE OF THE |
| | SPACE PURSUANT TO EITHER THE CODE ITSELF OF ASHRAE |
| | 62-04. PLEASE SHOW THE BASIS/METHODOLOGY UTILIZED FOR |
| | YOUR CALCUATION. |
| | 2. THE PROJECT MANUAL N REFLECTS SOLAR AND TRANSMISSION |
| | HEAT GAINS IN NORTH AND EAST DIRECTIONS, BUT THE |
| | PROJECT APPEARS TO BE CONFIGURED WITH GLAZING |
| | PREDOMINATELY LOCATED IN THE SOUTH AND WEST |
| | ORIENTATIONS, BOTH OF WHICH APPEAR TO REFLECT THE |
| | "WORST CASE" SCENARIO. PLEASE CHECK ALL TRANSMISSION |
| | GAIN COMPONENTS LISTED IN THE MANUAL N FOR VALIDITY |
| | WITHIN THE PROPOSED STRUCTURE AND COORDINATE. |
| | 3. THE PROJECT MANUAL N REFLECTS 23 PERSONS FOR HEAT |
| | GAIN WHILE THE ACTUAL FLOOR PLAN REFLECTS 35 SEATS. |
| | PLEASE COORDINATE WITH THE DESIGN COMPONENTS. |
| | 4. THE PROJECT MANUAL N REFLECTS 1200 WATTS FLOURESCENT |
| | LIGHTING WHILE THE ELECTRICAL PLAN INDICATES 1910 WATTS |
| | TOTAL WITH 710 WATTS BEING FLOURESCENT AND 1200 WATTS |
| | BEING IN INCANDESCENT, LED, OR POSSIBLY HALOGEN. PLEASE |
| | REVIEW AND COORDINATE MANUAL N CALCULATIONS WITH THE |
| | PROJECT PLANS AND PROVIDE SPECIFICATIONS ON THE |
| | PROPOSED "HIGH HAT" LIGHTING FIXTURES TO BE INSTALLED. |
| | 5. A JUMPER DUCT TO FACILITATE AIR SUPPLY TO THE MEN'S |
| | RESTROOM IS INDICTED ON SHEET M-1 BUT NO INFORMATION IS |
| | PROVIDED FOR A JUMPER DUCT SERVING THE WOMEN'S |
| | RESTROOM. IS THIS JUMPER ALREADY EXISTING? THIS SEEMS |
| | IMPROBABLE AS THE GRID CEILING APPEARS TO BE NEW IN THE |
| | CORRIDOR AS WELL AS THE WOMEN'S RESTROOM GIVEN THAT AT |
| | LEAST ONE WALL IN THE WOMENS RESTROOM IS BEING |
| | RELOCATED AS PART OF THIS PROJECT. PLEASE CLARIFY. |
| | |