2010-03-22 14:34:02MECHANICAL PLAN REVIEW COMMENTS:
  
 1. ASHRAE -62-04 FRESH AIR CALCULATION - THE SPACE HAS
 BEEN IMPROPERLY CLASSIFIED PURSUANT TO EITHER ASHRAE
 62-04 OR FBCM AS A "MERCANTILE" SPACE. THIS IS THE
 BUILDING CODE CLASSIFICATION OF THE PROPOSED OCCUPANCY
 AND IS NOT APPLICABLE TO THE REQUIRED VENTILATION RATES
 FOR THE INTENDED USE. PLEASE REVISE THE FRESH AIR
 CALCULATIONS TO ACCURATELY REFLECT THE USAGE OF THE
 SPACE PURSUANT TO EITHER THE CODE ITSELF OF ASHRAE
 62-04. PLEASE SHOW THE BASIS/METHODOLOGY UTILIZED FOR
 YOUR CALCUATION.
 2. THE PROJECT MANUAL N REFLECTS SOLAR AND TRANSMISSION
 HEAT GAINS IN NORTH AND EAST DIRECTIONS, BUT THE
 PROJECT APPEARS TO BE CONFIGURED WITH GLAZING
 PREDOMINATELY LOCATED IN THE SOUTH AND WEST
 ORIENTATIONS, BOTH OF WHICH APPEAR TO REFLECT THE
 "WORST CASE" SCENARIO. PLEASE CHECK ALL TRANSMISSION
 GAIN COMPONENTS LISTED IN THE MANUAL N FOR VALIDITY
 WITHIN THE PROPOSED STRUCTURE AND COORDINATE.
 3. THE PROJECT MANUAL N REFLECTS 23 PERSONS FOR HEAT
 GAIN WHILE THE ACTUAL FLOOR PLAN REFLECTS 35 SEATS.
 PLEASE COORDINATE WITH THE DESIGN COMPONENTS.
 4. THE PROJECT MANUAL N REFLECTS 1200 WATTS FLOURESCENT
 LIGHTING WHILE THE ELECTRICAL PLAN INDICATES 1910 WATTS
 TOTAL WITH 710 WATTS BEING FLOURESCENT AND 1200 WATTS
 BEING IN INCANDESCENT, LED, OR POSSIBLY HALOGEN. PLEASE
 REVIEW AND COORDINATE MANUAL N CALCULATIONS WITH THE
 PROJECT PLANS AND PROVIDE SPECIFICATIONS ON THE
 PROPOSED "HIGH HAT" LIGHTING FIXTURES TO BE INSTALLED.
 5. A JUMPER DUCT TO FACILITATE AIR SUPPLY TO THE MEN'S
 RESTROOM IS INDICTED ON SHEET M-1 BUT NO INFORMATION IS
 PROVIDED FOR A JUMPER DUCT SERVING THE WOMEN'S
 RESTROOM. IS THIS JUMPER ALREADY EXISTING? THIS SEEMS
 IMPROBABLE AS THE GRID CEILING APPEARS TO BE NEW IN THE
 CORRIDOR AS WELL AS THE WOMEN'S RESTROOM GIVEN THAT AT
 LEAST ONE WALL IN THE WOMENS RESTROOM IS BEING
 RELOCATED AS PART OF THIS PROJECT. PLEASE CLARIFY.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6650 DURING
 NORMAL BUSINESS HOURS WITH QUESTIONS OR CONCERNS ABOUT
 ANY OF THESE ISSUES. I MAY ALSO BE REACHED BY EMAIL AT
 [email protected].
  
 THANK YOU,
  
 DOUG WISE
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved