| Plan Review Notes For Permit 10020532 |
| Permit Number |
10020532 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-12 15:11:04 | *****DENIED***** | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS TO COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 2. THE 2006 EDITION OF NFPA 101 - LIFE SAFETY CODE - | | | SHALL BE REFERENCED. | | | | | | 3. NO POINT OF COMPASS INDICATED ON THE FLOOR PLAN | | | SHEET(S). | | | | | | 4. NO EXIT LIGHTS AND/OR EMERGENCY LIGHTS SHOWN ON THE | | | LIGHTING PLAN (SHEET E-2.0). | | | | | | 5. HOW WILL THE SCOPE OF WORK CAUSE MODIFICATION TO THE | | | FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|