 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 ALL COMMENTS RELATE TO SHEETS E-1.0 & E-2.0, UNLESS
 OTHERWISE NOTED. ALL CODE ARTICLES REFERENCED ARE 2008
 NEC UNLESS OTHERWISE NOTED.
  
 1} THE NOTES ON SHEET E-1.0#1 & 11 INCORRECTLY
 REFERENCE CODES FOR WHICH ARE NOT CURRENT FOR THIS
 PROJECT APPLICATION DATE, SEE REFERENCE STANDARDS
 ABOVE. THE REFERENCES TO CHAPTER 13 INTHE NOTES ARE
 FROM THE 2004 FBC, SEE 2007 FBC.
  
 2} PER CHAPTER 13 FBC SEE THE FOLLOWING: 13-415.AB.5
 INTERIOR LIGHTING POWER, SCOPE. THE INTERIOR LIGHTING
 POWER ALLOWANCE FOR A BUILDING OR A SEPARATELY METERED
 OR PERMITTED PORTION OF A BUILDING SHALL BE DETERMINED
 BY THE SPACE-BY-SPACE METHOD DESCRIBED IN SECTION
 13-415.B.1. TRADE-OFFS OF INTERIOR LIGHTING POWER
 ALLOWANCE AMONG PORTIONS OF THE BUILDING FOR WHICH A
 DIFFERENT METHOD OF CALCULATION HAS BEEN USED ARE NOT
 PERMITTED. THE INSTALLED INTERIOR LIGHTING POWER
 IDENTIFIED IN ACCORDANCE WITH SECTION 13-415.AB.5.1
 SHALL NOT EXCEED THE INTERIOR LIGHTING POWER ALLOWANCE
 DEVELOPED IN ACCORDANCE WITH SECTION13-415.B.1*** SHOW
 COMPLIANCE ON THE PLAN. THIS CAN BE DEMONSTRATED ON THE
 PLANS INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN
 FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
 INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE
 WITH THE ONES IN THE CALCULATIONS.
  
 3} 13-415.1.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED
 BY CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE
 CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL
 LIGHTING WITHIN THE SPACE. SEE BATHROOMS.NOTE \: THE
 SINGLE POLE SWITCHES SHOWN ON THE PLAN WILL NOT
 CORRECTLY OVERIDE THE TIME CLOCK FOR NO MORE THAN FOUR
 HOURS. 13-415.AB.1.2 B
  
 4} CIRCUIT A5 IN THE WINE BAR IS LISTED AS A "SPACE" ON
 THE PANEL SCHEDULE.
  
 5} CIRCUIT A7 IN THE KITCHEN IS LISTED AS A "SPACE" ON
 THE PANEL SCHEDULE.
  
 6} CIRCUIT B18,20 FOR THE DISHWASHER IS ON A 20 AMP
 BREAKER FED WITH # 12 CU WIRE. THE EQUIPMENT SCHEDULE
 LISTS THE DISHWASHER @32 AMPS.SEE 310.16 FOR WIRE SIZE,
 CORRELATE WITH EQUIPMENT SCHEDULE.
  
 7} THE AIR HANDLER ON SHEET M-1.0 IS LISTED AS 460
 VOLTS/3PHASE. THE IS LISTED @ 120/208 VOLTS 3
 PHASE.BOTH THE A/C AND CONDENSOR ARE SINGLE PHASE 208
 ON THE PANEL SCHEDULE. CORRELATE AND INDICATE WHAT THE
 EXISTING UNIT IS.
  
 8} CIRCUIT B32 IS SHOWN AS SERVING THE FLOOR MIXER IN
 THE KITCHEN AND ALSO THE WATER HEATER.408.4 NEC
  
 9} 220.14 (F) SIGN AND OUTLINE LIGHTING SIGN AND
 OUTLINE LIGHTING OUTLETS SHALL BE CALCULATED AT A
 MINIMUM OF 1200 VOLT-AMPERES FOR EACH REQUIRED BRANCH
 CIRCUIT SPECIFIED IN 600.5(A).NONE SHOWN ON THE PANEL
 SCHEDULE OR IN THE CALCULATIONS
  
 10} 220.14(G) SHOW WINDOWS SHOW WINDOWS SHALL BE
 CALCULATED IN ACCORDANCE WITH EITHER OF THE FOLLOWING:
 (1) THE UNIT LOAD PER OUTLET AS REQUIRED IN OTHER
 PROVISIONS OF THIS SECTION
 (2) AT 200 VOLT-AMPERES PER 300 MM (1 FT) OF SHOW
 WINDOW
 THERE APPEARS TO BE 16' OF SHOW WINDOW ON THE SOUTH
 SIDE OF THE BUILDING. THE RECEPTACLES INSTALLED TO
 COMPLY WITH THIS ARTICLE MUST ALSO COMPLY WITH 408.4 ,
 IDENTIFICATION.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  