| 2010-03-04 14:06:24 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008 |
| | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING |
| | |
| | ALL COMMENTS RELATE TO SHEETS E-1.0 & E-2.0, UNLESS |
| | OTHERWISE NOTED. ALL CODE ARTICLES REFERENCED ARE 2008 |
| | NEC UNLESS OTHERWISE NOTED. |
| | |
| | 1} THE NOTES ON SHEET E-1.0#1 & 11 INCORRECTLY |
| | REFERENCE CODES FOR WHICH ARE NOT CURRENT FOR THIS |
| | PROJECT APPLICATION DATE, SEE REFERENCE STANDARDS |
| | ABOVE. THE REFERENCES TO CHAPTER 13 INTHE NOTES ARE |
| | FROM THE 2004 FBC, SEE 2007 FBC. |
| | |
| | 2} PER CHAPTER 13 FBC SEE THE FOLLOWING: 13-415.AB.5 |
| | INTERIOR LIGHTING POWER, SCOPE. THE INTERIOR LIGHTING |
| | POWER ALLOWANCE FOR A BUILDING OR A SEPARATELY METERED |
| | OR PERMITTED PORTION OF A BUILDING SHALL BE DETERMINED |
| | BY THE SPACE-BY-SPACE METHOD DESCRIBED IN SECTION |
| | 13-415.B.1. TRADE-OFFS OF INTERIOR LIGHTING POWER |
| | ALLOWANCE AMONG PORTIONS OF THE BUILDING FOR WHICH A |
| | DIFFERENT METHOD OF CALCULATION HAS BEEN USED ARE NOT |
| | PERMITTED. THE INSTALLED INTERIOR LIGHTING POWER |
| | IDENTIFIED IN ACCORDANCE WITH SECTION 13-415.AB.5.1 |
| | SHALL NOT EXCEED THE INTERIOR LIGHTING POWER ALLOWANCE |
| | DEVELOPED IN ACCORDANCE WITH SECTION13-415.B.1*** SHOW |
| | COMPLIANCE ON THE PLAN. THIS CAN BE DEMONSTRATED ON THE |
| | PLANS INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN |
| | FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS. |
| | INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE |
| | WITH THE ONES IN THE CALCULATIONS. |
| | |
| | 3} 13-415.1.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED |
| | BY CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE |
| | CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL |
| | LIGHTING WITHIN THE SPACE. SEE BATHROOMS.NOTE \: THE |
| | SINGLE POLE SWITCHES SHOWN ON THE PLAN WILL NOT |
| | CORRECTLY OVERIDE THE TIME CLOCK FOR NO MORE THAN FOUR |
| | HOURS. 13-415.AB.1.2 B |
| | |
| | 4} CIRCUIT A5 IN THE WINE BAR IS LISTED AS A "SPACE" ON |
| | THE PANEL SCHEDULE. |
| | |
| | 5} CIRCUIT A7 IN THE KITCHEN IS LISTED AS A "SPACE" ON |
| | THE PANEL SCHEDULE. |
| | |
| | 6} CIRCUIT B18,20 FOR THE DISHWASHER IS ON A 20 AMP |
| | BREAKER FED WITH # 12 CU WIRE. THE EQUIPMENT SCHEDULE |
| | LISTS THE DISHWASHER @32 AMPS.SEE 310.16 FOR WIRE SIZE, |
| | CORRELATE WITH EQUIPMENT SCHEDULE. |
| | |
| | 7} THE AIR HANDLER ON SHEET M-1.0 IS LISTED AS 460 |
| | VOLTS/3PHASE. THE IS LISTED @ 120/208 VOLTS 3 |
| | PHASE.BOTH THE A/C AND CONDENSOR ARE SINGLE PHASE 208 |
| | ON THE PANEL SCHEDULE. CORRELATE AND INDICATE WHAT THE |
| | EXISTING UNIT IS. |
| | |
| | 8} CIRCUIT B32 IS SHOWN AS SERVING THE FLOOR MIXER IN |
| | THE KITCHEN AND ALSO THE WATER HEATER.408.4 NEC |
| | |
| | 9} 220.14 (F) SIGN AND OUTLINE LIGHTING SIGN AND |
| | OUTLINE LIGHTING OUTLETS SHALL BE CALCULATED AT A |
| | MINIMUM OF 1200 VOLT-AMPERES FOR EACH REQUIRED BRANCH |
| | CIRCUIT SPECIFIED IN 600.5(A).NONE SHOWN ON THE PANEL |
| | SCHEDULE OR IN THE CALCULATIONS |
| | |
| | 10} 220.14(G) SHOW WINDOWS SHOW WINDOWS SHALL BE |
| | CALCULATED IN ACCORDANCE WITH EITHER OF THE FOLLOWING: |
| | (1) THE UNIT LOAD PER OUTLET AS REQUIRED IN OTHER |
| | PROVISIONS OF THIS SECTION |
| | (2) AT 200 VOLT-AMPERES PER 300 MM (1 FT) OF SHOW |
| | WINDOW |
| | THERE APPEARS TO BE 16' OF SHOW WINDOW ON THE SOUTH |
| | SIDE OF THE BUILDING. THE RECEPTACLES INSTALLED TO |
| | COMPLY WITH THIS ARTICLE MUST ALSO COMPLY WITH 408.4 , |
| | IDENTIFICATION. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |
| | |
| | |
| | |
| | |