| Plan Review Notes For Permit 10020532 |
| Permit Number |
10020532 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-09 09:18:46 | BUILDING REVIEW COMMENTS | | | | | | | | | 1) | | | PALM BEACH COUNTY IMPACT FEES WILL BE REQUIRED. | | | | | | 2) | | | SHEET TS-1 SHOWS 2 EXISTING FIXED WINDOWS AT THE WEST | | | ELEVATION, FLOOR PLAN INDICATES 1. PROVIDE SURVEY TO | | | VERIFY WEST ELEVATION IS NOT A '0' LOT LINE. | | | | | | 3) | | | ENERGY CALCULATIONS CALL FOR A SOLID CORE ENTRY DOOR, | | | THE PLANS INDICATE AN EXISTING GLASS ENTRY DOOR ? THE | | | CALCULATIONS ALSO REFERENCE A METAL BUILDING WITH R/19 | | | ROOF INSULATION ? | | | | | | 4) | | | SHEET A-1-0 FINISH NOTE # 10 CALLS FOR 1 3/4" SOLID | | | CORE DOORS, IF THAT IS THE CASE THEN YOUR 2'10" | | | INTERIOR DOORS WILL NOT MEET THE MINIMUM 32" CLEAR | | | WIDTH REQUIREMENT OF 11-4.13.5 FBC 2007. | | | | | | | | | | | | | | | | | | LUIS MARTINEZ | | | 561-805-6710 | | | | | | | | | |
|