| Plan Review Notes For Permit 10020525 |
| Permit Number |
10020525 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-03-29 12:30:53 | 2ND REVIEW | | | ACTION: DENIED | | | | | | FBC PLUMBING 2007 | | | | | | 1. WATER CLOSETS ARE NOT VENTED PROPERLY. ADDING A | | | VERTICAL DRY VENT IN THE WALL OF ROOM #110 WOULD BE | | | ACCEPTABLE. | | | 909.1 WET VENT -ONLY THE FIXTURES WITHIN THE BATHROOM | | | GROUPS SHALL CONNECT TO THE WET-VENTED HORIZONTAL | | | BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. | | | | | | 2. THE COMBINATION DRAIN AND VENT SHOWN FOR THE LAVS, | | | DF, AND SINK IS NOT SIZED - MINIMUM 2 1/2" REQUIRED. | | | 912.3 THE MINIMUM SIZE OF A COMBINATION DRAIN AND VENT | | | PIPE SHALL BE IN ACCORDANCE WITH TABLE 912.3. | | | | | | 3. 603.1 3/4" COLD WATER PIPE IS REQUIRED FOR MORE THAN | | | TWO FIXTURES UP TO 18 FIXTURE UNITS. 604.5 MINIMUM PIPE | | | SIZE FOR THE SINK FIXTURE DROP IS 1/2". | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|