2010-03-29 12:30:532ND REVIEW
 ACTION: DENIED
  
 FBC PLUMBING 2007
  
 1. WATER CLOSETS ARE NOT VENTED PROPERLY. ADDING A
 VERTICAL DRY VENT IN THE WALL OF ROOM #110 WOULD BE
 ACCEPTABLE.
 909.1 WET VENT -ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUPS SHALL CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT.
  
 2. THE COMBINATION DRAIN AND VENT SHOWN FOR THE LAVS,
 DF, AND SINK IS NOT SIZED - MINIMUM 2 1/2" REQUIRED.
 912.3 THE MINIMUM SIZE OF A COMBINATION DRAIN AND VENT
 PIPE SHALL BE IN ACCORDANCE WITH TABLE 912.3.
  
 3. 603.1 3/4" COLD WATER PIPE IS REQUIRED FOR MORE THAN
 TWO FIXTURES UP TO 18 FIXTURE UNITS. 604.5 MINIMUM PIPE
 SIZE FOR THE SINK FIXTURE DROP IS 1/2".
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR