Plan Review Notes
Plan Review Notes For Permit 10020525
Permit Number 10020525
Review Stop P
Sequence Number 1
Notes
Date Text
2010-03-03 09:05:54DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 BUILDING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS SHALL INDICATE THE ARCHITECTURAL BUSINESS
 NUMBER, (CERTIFICATE OF AUTHORIZATION), IN THE TITLE
 BLOCK OF EACH SHEET. (AA26001535). ALSO THE DATE THE
 SEAL AND SIGNATURE ARE AFFIXED TO EACH SHEET SHALL BE
 INDICATED BELOW THE SIGNATURE. FAC 61G1-16.004(2)(5) &
 FS 481.2055.
  
 2. SHT A-2 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. (SEE SECTION 410.1). PLEASE SHOW THE LOCATION OF
 THE REQUIRED D.F. AND SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 3. SHT A-2 RESTROOM 110 SHALL BE ACCESSIBLE. SECTION
 11-4.1.3(11). SUBMIT A DETAIL FOR THE TOILET ROOM
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
  
 4. SHT A-2 THE BREAKROOM SINK SHALL BE ACCESSIBLE.
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24
 WITH ALL SUBSECTIONS. (NOTE: FORWARD APPROACH CLEAR
 FLOOR SPACE REQUIRED, CABINET DOORS NOT APPROVED IN
 CLEAR FLOOR SPACE).
  
 5. SHT A-2 ROOM 113 SHOWS A WATER HEATER IN THE SUPPLY
 CLOSET. PER NFPA SECTION 422.17, PROTECTION OF
 COMBUSTIBLE MATERIAL, EACH ELECTRICALLY HEATED
 APPLIANCE THAT IS INTENDED BY SIZE, WEIGHT, AND SERVICE
 TO BE LOCATED IN A FIXED POSITION SHALL BE PLACED SO AS
 TO PROVIDE AMPLE PROTECTION BETWEEN THE APPLIANCE AND
 ADJACENT COMBUSTIBLE MATERIAL. PLEASE INDICATE THE
 METHOD OF PROTECTION.
  
 6. SHT A-5 DETAIL 5 SHOWS THE TOILET PAPER DISPENSER TO
 BE INSTALLED ABOVE THE FLOOR 17" - 19". PER FIGURE 29
 THE DISPENSER SHALL BE LOCATED MINIMUM 19" ABOVE THE
 FLOOR. PLEASE CORRECT THE DETAIL.
  
 7. SHT A-5 DETAIL 4 SHOW COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 8. SHT A-6 FINISH ROOM SCHEDULE. TOILET ROOMS 107 & 110
 WALL SCHEDULE SHALL MEET THE REQUIREMENT OF SECTION
 1210.2
 1210.2 WALLS. WALLS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. -- PLANS
 SHOW PAINTED WALLS WHICH DOES NOT COMPLY. PLEASE
 INDICATE METHOD OF COMPLIANCE.
  
 9. SHT P-1 A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED
 PER SECTION 106.3.5.1.3. PLEASE SUBMIT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved