| Date |
Text |
| 2010-03-03 09:05:54 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 BUILDING |
| | FBC-2007 CHAPTER 1 |
| | FBC-2007 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS SHALL INDICATE THE ARCHITECTURAL BUSINESS |
| | NUMBER, (CERTIFICATE OF AUTHORIZATION), IN THE TITLE |
| | BLOCK OF EACH SHEET. (AA26001535). ALSO THE DATE THE |
| | SEAL AND SIGNATURE ARE AFFIXED TO EACH SHEET SHALL BE |
| | INDICATED BELOW THE SIGNATURE. FAC 61G1-16.004(2)(5) & |
| | FS 481.2055. |
| | |
| | 2. SHT A-2 A DRINKING FOUNTAIN IS REQUIRED PER TABLE |
| | 403.1. (SEE SECTION 410.1). PLEASE SHOW THE LOCATION OF |
| | THE REQUIRED D.F. AND SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS |
| | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 3. SHT A-2 RESTROOM 110 SHALL BE ACCESSIBLE. SECTION |
| | 11-4.1.3(11). SUBMIT A DETAIL FOR THE TOILET ROOM |
| | SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & |
| | 11-4.22 WITH ALL SUBSECTIONS. |
| | |
| | 4. SHT A-2 THE BREAKROOM SINK SHALL BE ACCESSIBLE. |
| | SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24 |
| | WITH ALL SUBSECTIONS. (NOTE: FORWARD APPROACH CLEAR |
| | FLOOR SPACE REQUIRED, CABINET DOORS NOT APPROVED IN |
| | CLEAR FLOOR SPACE). |
| | |
| | 5. SHT A-2 ROOM 113 SHOWS A WATER HEATER IN THE SUPPLY |
| | CLOSET. PER NFPA SECTION 422.17, PROTECTION OF |
| | COMBUSTIBLE MATERIAL, EACH ELECTRICALLY HEATED |
| | APPLIANCE THAT IS INTENDED BY SIZE, WEIGHT, AND SERVICE |
| | TO BE LOCATED IN A FIXED POSITION SHALL BE PLACED SO AS |
| | TO PROVIDE AMPLE PROTECTION BETWEEN THE APPLIANCE AND |
| | ADJACENT COMBUSTIBLE MATERIAL. PLEASE INDICATE THE |
| | METHOD OF PROTECTION. |
| | |
| | 6. SHT A-5 DETAIL 5 SHOWS THE TOILET PAPER DISPENSER TO |
| | BE INSTALLED ABOVE THE FLOOR 17" - 19". PER FIGURE 29 |
| | THE DISPENSER SHALL BE LOCATED MINIMUM 19" ABOVE THE |
| | FLOOR. PLEASE CORRECT THE DETAIL. |
| | |
| | 7. SHT A-5 DETAIL 4 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | A. 11-4.19.2 CLEARANCES |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | |
| | 8. SHT A-6 FINISH ROOM SCHEDULE. TOILET ROOMS 107 & 110 |
| | WALL SCHEDULE SHALL MEET THE REQUIREMENT OF SECTION |
| | 1210.2 |
| | 1210.2 WALLS. WALLS WITHIN 2 FEET (610 MM) OF URINALS |
| | AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) |
| | ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, |
| | THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE |
| | THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. -- PLANS |
| | SHOW PAINTED WALLS WHICH DOES NOT COMPLY. PLEASE |
| | INDICATE METHOD OF COMPLIANCE. |
| | |
| | 9. SHT P-1 A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED |
| | PER SECTION 106.3.5.1.3. PLEASE SUBMIT. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |