2010-03-03 11:10:02REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. FLOOR PLAN HAS MULTIPLE DUCTS MISSING SIZE AND/OR
 CFM DESIGNATIONS, INCLUDING FRESH AIR DUCT FOR AHU 2.
 PROVIDE ALL MISSING INFORMATION PER FBC-M 603.1.
  
 2. RETURN AIR TRANSFER DUCTS ARE NOT SIZED TO MEET THE
 BALANCED RETURN EXCEPTIONS UNDER FBC-M 601.4. SHOW HOW
 BALANCED RETURN IS TO BE ACHIEVED IN THESE AREAS.
  
 3. PLAN SHOWS EXISTING FIRE DAMPERS TO REMAIN EVEN
 THOUGH RATED WALLS ARE REMOVED. FIRE DAMPERS ARE TO BE
 INSTALLED IN ACCORDANCE WITH THEIR LISTING WITIN A
 RATED WALL ASSEMBLY. REMOVE OR SHOW HOW A COMPLIANT
 IJNSTALLATION WILL BE ACHIEVED PER FBC-M 607.2.
  
 4. PLANS REFERENCE THE 2004 FBC. PLEASE UPDATE ALL CODE
 REFERENCES TO REFLECT THE CODE IN EFFECT AT TIME OF
 PERMIT APPLICATION.
  