| 2010-03-03 11:10:02 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. FLOOR PLAN HAS MULTIPLE DUCTS MISSING SIZE AND/OR | | | CFM DESIGNATIONS, INCLUDING FRESH AIR DUCT FOR AHU 2. | | | PROVIDE ALL MISSING INFORMATION PER FBC-M 603.1. | | | | | | 2. RETURN AIR TRANSFER DUCTS ARE NOT SIZED TO MEET THE | | | BALANCED RETURN EXCEPTIONS UNDER FBC-M 601.4. SHOW HOW | | | BALANCED RETURN IS TO BE ACHIEVED IN THESE AREAS. | | | | | | 3. PLAN SHOWS EXISTING FIRE DAMPERS TO REMAIN EVEN | | | THOUGH RATED WALLS ARE REMOVED. FIRE DAMPERS ARE TO BE | | | INSTALLED IN ACCORDANCE WITH THEIR LISTING WITIN A | | | RATED WALL ASSEMBLY. REMOVE OR SHOW HOW A COMPLIANT | | | IJNSTALLATION WILL BE ACHIEVED PER FBC-M 607.2. | | | | | | 4. PLANS REFERENCE THE 2004 FBC. PLEASE UPDATE ALL CODE | | | REFERENCES TO REFLECT THE CODE IN EFFECT AT TIME OF | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|