| Plan Review Notes For Permit 10020525 |
| Permit Number |
10020525 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-05 15:43:55 | *****DENIED***** | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS TO COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 2. NFPA 101, LIFE SAFETY CODE, SHALL BE REFERENCED. | | | | | | 3. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW | | | WALLS AND/OR CEILINGS IN TERMS OF CLASS A, CLASS B, OR | | | CLASS C. | | | | | | 4. ACCORDING TO THE DOOR AND FRAME SCHEDULE, AS LISTED | | | ON SHEET A-2, IT LISTS ROOM 102 AS A STORAGE ROOM | | | WHEREAS THE PROPOSED FLOOR PLAN HAS IT LISTED AS AN | | | ELECTRICAL ROOM. PLEASE EXPLAIN. | | | | | | 5. IN REFERENCE TO DOOR EIGHT (D-8) AS LISTED ON SHEET | | | A-2, HOW WILL EXITING AT THAT DOOR BE ACOMPLISHED? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADSDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|