Date Text
2010-03-04 10:14:35 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 ALL COMMENTS RELATE TO SHEET E-1 & E-2, UNLESS
 OTHERWISE NOTED. ALL CODE ARTICLES REFERENCED ARE 2008
 NEC UNLESS OTHERWISE NOTED.
  
 SHOW COMPLIANCE WITH THE FOLLOWING CHAPTER 13 ARTICLES
 20070FBC
  
 1} 13-415.AB MANDATORY REQUIREMENTS FOR METHODS A AND B
 13-415.AB.1 CONTROLS
 13-415.AB.1.1 AUTOMATIC LIGHTING CONTROLS. INTERIOR
 LIGHTING IN BUILDINGS LARGER THAN 5,000 SQUARE FEET
 (465 M2) SHALL BE CONTROLLED WITH AN AUTOMATIC CONTROL
 DEVICE TO SHUT OFF BUILDING LIGHTING IN ALL SPACES.
 THIS AUTOMATIC CONTROL DEVICE SHALL FUNCTION ON EITHER:
 1. A SCHEDULED BASIS USING A TIME-OF-DAY OPERATED
 CONTROL DEVICE THAT TURNS LIGHTING OFF AT SPECIFIC
 PROGRAMMED TIMES???AN INDEPENDENT PROGRAM SCHEDULE
 SHALL BE PROVIDED FOR AREAS OF NO MORE THAN 25,000
 SQUARE FEET (2323 M2) BUT NOT MORE THAN ONE FLOOR.
 2. AN OCCUPANT SENSOR THAT SHALL TURN LIGHTING OFF
 WITHIN 30 MINUTES OF AN OCCUPANT LEAVING A SPACE.
  
 2} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1*** SHOW COMPLIANCE ON THE PLAN. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATING THE
 WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT
 CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES
 ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS.408.4 CIRCUIT DIRECTORY OR CIRCUIT
 IDENTIFICATION
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.
  
 3} 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL
 BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON
 THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANELBOARD, AND LOCATED AT EACH SWITCH ON A
 SWITCHBOARD.
  
 4} PER 700.12(F)(4)-THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES. THE BRANCH CIRCUIT THAT
 FEEDS UNIT EQUIPMENT SHALL BE CLEARLY IDENTIFIED AT THE
 DISTRIBUTION PANEL.INDICATE SAME ON THE PLAN, LOCATE
 THE EMERGENCY LIGHTING.
  