| Plan Review Notes For Permit 10020511 |
| Permit Number |
10020511 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-02-23 15:07:16 | REROOF BUILDING REVIEW CHECKLIST | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- A) CLEARLY SPECIFY WHICH APPROVED ASSEMBLY FROM | | | CERTAINTEED CORPORATION NOA 04-0623.01 IS GOING TO BE | | | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. 1609 OF FBC 2007 WITH 2009 REVISIONS. | | | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. | | | | | | 2- A) FILE FOR GAF NOA 07-1203.01 SUBMITTED IS | | | SUPERSEDED. SEE MIAMI-DADE WEBSITE. PROVIDE CURRENT | | | NOA. | | | | | | B) CLEARLY SPECIFY WHICH BASE SHEET FASTENING OPTION IS | | | GOING TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. 1609 FBC 2007 WITH 2009 REVISIONS. | | | | | | C) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|