| Plan Review Notes For Permit 10020496 |
| Permit Number |
10020496 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-08 10:06:36 | 1885 OKEECHOBEE ROAD | | | ARMOR SCREEN CORPORATION | | | PERMIT # 10020496 | | | | | | 1. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY | | | WITH NFPA 241. | | | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER SYSTEM REMODEL. | | | | | | 3. NO FIRE ALARM DEVICES SHOWN IN EXISTING WORK AREA, | | | EMPLOYEE LOUNGE, AND NEW CONFERENCE ROOM. | | | | | | 4. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE | | | ALARM REMODELING PLANNED. | | | | | | 5. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | 6. PLEASE INDICATE EXISTING HARDWARE AND LOCKING | | | DEVICES PRESENT ON EXISTING EXIT DOORS. | | | | | | 7. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND | | | CEILINGS SHALL COMPLY WITH THE FLORIDA BUILDING AND | | | FLORIDA FIRE PREVENTION CODE. | | | | | | 8. MORE DETAILS REQUIRED FOR NEW COMPUTER ROOM. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | (561) 804-4709 PHONE | | | (561) 804-4774 |
|