| 2010-03-01 16:58:16 | ** DENIED ** |
| | |
| | |
| | 1) NOTE: THE APPLIED VALUE FOR THE COMPLETE SCOPE OF |
| | WORK SHOWN ON PLANS IS LOW. |
| | PLEASE KNOW THAT PER FBC 108.3 THE APPLIED SCOPE OF |
| | WORK IS TO INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, |
| | DESIGN COST EVEN IF ANY OF THESE THINGS ARE OWNER |
| | SUPPLIED. |
| | |
| | 2) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR NEW |
| | AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. |
| | 408.4,310.16,240.4, 220, 210 ETC |
| | THE CIRCUITING ON PANEL SCHEDULES ARE NOT PERMITTED TO |
| | BE GENERIC. * LIGHTING AND RECEPTACLES * IS NOT |
| | ACCEPTABLE. PLEASE SEE CODE COMMENTARY IN THE NEC UNDER |
| | 408.4. |
| | |
| | 3) NOTE: PLEASE PLACE NOTE ON PLANS FOR COMPUTER ROOM. |
| | * NO NEC 645 WIRING METHODS PERMITTED* OR WORDS TO THAT |
| | AFFECT. |
| | THIS IS NOT AN IT ROOM BY DEFINITION BASED ON THE PLANS |
| | SUBMITTED THEREFORE WIRING METHODS WHICH ARE LESS |
| | STRINGENT IN 645 ARE NOT ALLOWED. |
| | |
| | 4) NOTE: PLEASE SEE FBC 13-415.AB.1.1, .1.2 AND .1.3 |
| | FOR NEW LIGHTING CONTROLS. ANY NEW SEPARATE SPACES AND |
| | NEW CONTROLS SHALL MEET MINIMUM PRESCRIPTIVE |
| | REQUIREMENTS. |
| | |
| | 5) NOTE: PLANS INDICATE POWER FOR NEW EXHAUST FANS IN |
| | BATHROOMS HOWEVER NO CONTROL LOCATIONS SHOWN. |
| | PLEASE SEE MECHANICAL COMMENTS FOR FLORIDA MECHANICAL |
| | CODE WHICH REQUIRES CONTROLS. |
| | |
| | 6) NOTE: PLEASE SEE 240.21, 408.36 AS A MAIN IS |
| | REQUIRED ON THE SECONDARY SIDE OF THE TRANSFORMER. ALL |
| | TAPPED CONDUCTORS SHALL TERMINATE IN OVER CURRENT |
| | PROTECTION. |
| | THIS IS A LIFE SAFETY AND FIRE HAZARD AND WILL BE |
| | REQUIRED TO BE CORRECTED. |
| | |
| | 7) NOTE: LOADS ON SERVICE AND PANELS ARE TO BE |
| | COMPLETED. PANELS DO NOT INDICATE LOADS. |
| | 220, 220.14,220.12, 220.42, .43, ETC |
| | PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125%. |
| | |
| | 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS FOR NEW BEING INSTALLED IN ADDITION TO |
| | EXISTING IN NEW AREAS. |
| | 13-415.AB.5 |
| | |
| | 6) NOTE: HOW IS PANEL LA FED? THERE IS NO OCP SHOWN IN |
| | PANEL L FOR SUB PANEL. |
| | SEE NOTE #6 ABOVE. |
| | |
| | 7) NOTE: COVER SHEET INDICATES SOME CODES FROM THE 2004 |
| | FBC. PLEAS EBE SURE THE PLANS INDICATE THE FOLLOWING |
| | FOR THIS REVIEWER FOR RELEVANT DESIGN. |
| | |
| | |
| | 2007 FBC W/ 2009 SUPPLEMENTS |
| | 2006 NFPA-101 |
| | 2008 NFPA-70 |
| | 2002 NFPA-728) NOTE: NO FIRE ALARM DEVICES, SYSTEMS |
| | SHOWN. PLEASE SEE FBC 11-4.28.1,.2 AND .3 FOR MINIMUM |
| | LOCATIONS, LEVELS AND HEIGHTS FOR ADA COMPLIANCE. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |