Plan Review Notes
Plan Review Notes For Permit 10020492
Permit Number 10020492
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-03-10 10:40:39*****DENIED*****
  
 01. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 02. ON THE APPROPRIATE EXTERIOR ELEVATION FRONTING 9TH
 COURT, DISPLAY THE ADDRESS NUMBER OF THE PROJECT. AS
 PER WEST PALM BEACH CODE, ADDRESS NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH/STROKE.
  
 03. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION
 CODE WHICH IS BASED ON NFPA 101, LIFE SAFETY CODE, 2006
 EDITION AND NFPA 1, UNIFORM FIRE CODE, 2006 EDITION
 SHALL BE REFERENCED. THE FOLLOWING REVIEW COMMENTS ARE
 BASED ON CLASSIFICATION OF THIS STRUCTURE AS A NEW
 RESIDENTIAL BOARD AND CARE OCCUPANCY - SMALL FACILITY.
  
 04. PLEASE LIST THE NUMBER OF SLEEPING ACCOMMODATIONS
 FOR THE RESIDENTS/CLIENTS.
  
 05. PLEASE LIST THE CAPABILITY OF RESIDENTS/CLIENTS AS
 A GROUP TO MOVE RELIABLY TO A POINT OF SAFETY. BE
 ADVISED THAT A FIRE SPRINKLER SYSTEM SHALL NOT BE
 REQUIRED IN SMALL BOARD AND CARE HOMES SERVING EIGHT OR
 FEWER RESIDENTS WHEN ALL OCCUPANTS HAVE THE ABILITY TO
 AS A GROUP TO MOVE RELIABLY TO A POINT OF SAFETY WITHIN
 THREE MINUTES.
  
 06. SHOW THE LOCATION OF SMOKE ALARMS INSTALLED IN ALL
 LIVING AREAS AND SLEEPING ROOMS. SMOKE ALARMS (SA)
 SHALL RECEIVE THEIR OPERATING POWER FROM THE BUILDING
 ELECTRICAL SYSTEM WITH BATTERY BACK-UP.
  
 07. THE SMOKE ALARMS SHALL BE ARRANGED SO THAT
 OPERATION OF ANY SMOKE ALARM SHALL CAUSE THE ALARM
 WITHIN THE DWELLING UNIT TO SOUND.
  
 08. PROVIDE MANUAL FIRE ALARM SYSTEM AS PER NFPA 72 -
 2002 EDITION.
  
 09. SLEEPING ROOMS SHALL HAVE A SECOND MEANS OF ESCAPE
 IF IT DOES NOT HAVE A DOOR LEADING DIRECTLY TO THE
 OUTSIDE OF THE BUILDING. IT IS SHOWN ON SHEET 2 OF 3,
 25 EGS,S.H FOR THE BEDROOM WINDOWS. WHAT DOES THIS
 MEAN?
  
 10. EVERY CLOSET DOOR SHALL LATCH SHALL BE READILY
 OPENED FROM THE INSIDE.
  
 11. EVERY BATHROOM DOOR SHALL BE DESIGNED TO ALLOW
 OPENING FROM THE OUTSIDE DURING AN EMERGENCY WHEN
 LOCKED.
  
 12. SLEEPING ROOMS DOORS SHALL BE SUBSTANSIAL DOORS,
 SUCH AS THOSE OF 1 3/4" THICK, SOLID-BONDED WOOD CORE
 CONSTRUCTION OR OTHER CONSTRUCTION OF EQUAL OR GREATER
 STABILITY AND FIRE INTERGRITY. NOT SURE IF THE METAL
 BEDROOM DOORS SHOWN ON SHEET 2 OF 3 MEET THAT CRITERIA.
  
 13. PER NFPA 101 (LIFE SAFETY CODE, 2006 EDITION),
 SECTION 32.2.3.6.4 REQUIRES DOORS TO MEET THE FOLLOWING
 REQUIREMENTS:
 A) DOORS SHALL BE PROVIDED WITH LATCHES OR OTHER
 MECHANISMS SUITABLE FOR KEEPING THE DOORS CLOSED.
 B) NO DOORS SHALL BE ARRANGED TO PREVENT THE OCCUPANT
 FROM CLOSING THE DOORS.
 C) DOORS SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING IN
 ACCORDANCE WITH 7.2.1.8 IN BUILDINGS OTHER THAN THOSE
 PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM.
  
 14. PROVIDE LOCATIONS OF PORTABLE FIRE EXTINGUISHER(S)
 WHICH SATISFY THE 75 FOOT TRAVEL DISTANCE.
  
 15. PROVIDE POINT OF COMPASS ON PLANS.
  
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722