| 2010-03-23 16:22:25 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. THE NEW PLAN SHOWS 150MPH EXPOSURE B. PLEASE REVISE. |
| | |
| | 2. PLEASE CLARIFY GIRT SIZING. IF NECESSARY, CIRCLE ON |
| | THE CHARTS SUBMITTED. THE FIRST SUBMITTAL INCLUDED A |
| | SHEET WHICH PROVIDED GIRT INFORMATION; THIS WAS NOT |
| | PROVIDED IN A REVISED FORM FOR EXPOSURE C. HOWEVER, THE |
| | LOAD WIDTH APPEARS TOO SHORT (ROUNDING DOWN RATHER THAN |
| | ROUNDING UP) AND THE TYPE OF CHAIR RAIL PROPOSED IS NOT |
| | CLEAR, ONLY SIZE, BUT NOT ALL SIZES COMPLY. FOR |
| | INSTANCE, 4'4" LOAD WITDTH, 7'10" SPAN, 2X3. THE NEW |
| | PLAN DOES NOT SPECIFY WHICH 2X3; SMS IS SPECIFIED ON A |
| | SHEET FROM THE FIRST SUBMITTAL WHICH SPECIFIES EXPOSURE |
| | B. PLEASE REVISE THE PLAN TO INCLUDE THE TYPE OF GIRT |
| | PROPOSED. |
| | |
| | 4'4" LOAD WIDTH - IT APPEARS THAT THIS SHOULD BE 4'5". |
| | IT IS NOT CLEAR WHY YOU HAD SPECIFIED A 7'10" SPAN, |
| | ISN'T THIS AN 8' SPAN? YOU CANNOT DEDUCT FOR THE |
| | MEMBERS, THIS DIMENSION SHOULD GO FROM STRUCTURE/CENTER |
| | OF POST TO STRUCTURE/CENTER OF POST. 2X3 SMS REQUIRED, |
| | BUT "SMS" WAS NOT SPECIFIED ON ANY OF THE REVISED |
| | SHEETS. IT IS NOT CLEAR HOW SPANS HAVE BEEN DETERMINED. |
| | |
| | FOR THE 3'11"/5' LOAD WIDTH/SPAN, 2X2 SPECIFIED. SMS |
| | NOT SPECIFIED, BUT APPEARS TO BE REQUIRED. PLEASE |
| | REVISE PLAN TO STATE SPECIFIC SIZE IF ALL DO NOT |
| | COMPLY. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |